Relay Number Field
The Relay No. field allows a relay number (1-256) to be entered.
On tabbing out of the field:
 
The Galaxy No. field will show the relay number on the panel as LMMR where L is the
panel line number, MM is the module number on that line, and R is the relay number on
that module.
 
The system will check the relay state and display in the ‘State= ‘ field below.
 
Pressing the Relay On or Relay Off buttons will switch that relay.
Galaxy No. Field
The Galaxy No. field contains the relay number on the panel as LMMR where L is the panel line
number, MM is the module number on that line, and R is the relay number on that module. Typing
a relevant number and tabbing out of this field will cause the Relay No. field to change to the
equivalent number, and the Relay state= XX will show the state of that relay according to the panel.
Pressing the Relay On or Relay Off buttons will cause the relay to set or reset on the panel.
Relay On Button
If the relay Number field contains a valid relay number (1-256), pressing the Relay On button will
energise that relay.
Relay Off Button
If the relay Number field contains a valid relay number (1-256), pressing the Relay Off button will
de-energise that relay.
Panel Reset Required
If the Panel Reset Required check box is ticked then the system will send a reset back to the panel
when a Datalog alarm reset (F2 Key pressed) is initiated.
Troubleshooting
No Communications
 
Ensure the cable between the PC and the RS232 module is wired as per the installation
section of this document, and that it is connected.
 
Check the RS232 module is connected on Line 1 of the Galaxy panel and end of line
resistors fitted.
  Ensure that the RS232 module switches are set for correct baud rate/Data bits/stop
bits/Parity as per the installation section of this document.
 
Check that the correct Comm port is being used.
 
Ensure that Engineer option 56=COMMUNICATIONS has been set. See the installation
section of this document.
Communications but No Alarms On Remote Panel
 Check that the panel address has been set using Engineer option
56=COMMUNICATIONS has been set. See the installation section of this document.
Panel 1 is 000001, Panel 2 is 000002 etc
  Ensure the Alarm trigger(s) have been set to on using Engineer option
56=COMMUNICATIONS