Puls UC10.242 DIN-Rail UPS Техническое Руководство
UC10.241, UC10.242
UC-Series
24V,
15A,
C
APACITOR
-
BASED
B
UFFER
M
ODULES
22.6. S
ERIES
U
SE FOR
48V
A
PPLICATIONS
A series connection for 48V applications is allowed when utilizing two individual power supplies and two buffer
modules.
modules.
Fig. 22-4 Wiring example for 48V serial use
+ +
- -
Power
Supply
24V Output
+ +
- -
Power
Supply
24V Output
UC10
Buffer Module
IN
OUT
+
+
-
-
UC10
Buffer Module
IN
OUT
+
+
-
-
24/27
Inhibit
+
-
R
ead
y
B
u
fferin
g
M
ode
Inhibit
+
-
R
ead
y
B
u
fferin
g
M
ode
48V
Load
+
-
22.7. U
SING THE
I
NHIBIT
-I
NPUT
The inhibit-input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a
minimum length of 250ms is required to stop buffering. The inhibit signal is stored and can be reset by cycling the
input voltage.
minimum length of 250ms is required to stop buffering. The inhibit signal is stored and can be reset by cycling the
input voltage.
For service purposes, the inhibit input can also be used to connect a service switch. Therefore, the inhibit signal can be
supplied from the output of the buffer module.
supplied from the output of the buffer module.
Fig. 22-5 Wiring example for inhibit input
24V
Power
Supply
+
-
Buffered
Load
+
-
UC10
Buffer Module
OUT
IN
+
-
+
-
Service
Switch
Switch
In
h
ib
it
+ -
R
ea
d
y
B
u
ff
er
in
g
PC
M
o
d
e
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC)
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany