22.6.  S
ERIES 
U
SE FOR 
48V
 
A
PPLICATIONS
 
A series connection for 48V applications is allowed when utilizing two individual power supplies and two buffer 
modules. 
 
 
Fig. 22-4   Wiring example for 48V serial use 
 
 
+   +
-  -
Power
Supply
24V Output
+   +
-  -
Power
Supply
24V Output
UC10
Buffer Module
IN
OUT
+
+
-
-
UC10
Buffer Module
IN
OUT
+
+
-
-
24/27
Inhibit
+  
-
R
ead
y
B
u
fferin
g
 M
ode
Inhibit
+  
-
R
ead
y
B
u
fferin
g
 M
ode
48V
Load
+
-
 
 
 
22.7.  U
SING THE 
I
NHIBIT
-I
NPUT
 
The inhibit-input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a 
minimum length of 250ms is required to stop buffering. The inhibit signal is stored and can be reset by cycling the 
input voltage. 
For service purposes, the inhibit input can also be used to connect a service switch. Therefore, the inhibit signal can be 
supplied from the output of the buffer module. 
 
 
Fig. 22-5   Wiring example for inhibit input 
 
 
 
 24V
Power
Supply
+
-
Buffered
Load
+
-
UC10
Buffer Module
OUT
IN
+
-
+
-
Service
Switch
In
h
ib
it
+  -
R
ea
d
y
B
u
ff
er
in
g
PC
 M
o
d
e
 
 
 
Apr. 2014 / Rev. 2.0 DS-UC10.241-EN (REVC) 