Puls YRM2.DIODE Redundancy Module Техническое Руководство
YRM2.DIODE
Y-Series
DC24-48V,
20A,
D
UAL
R
EDUNDANCY
M
ODULE
8. F
UNCTIONAL
D
IAGRAM
Fig. 8-1 Functional diagram
+
-
+
-
+
-
Alarm
Relay
Relay
Input
Voltage
Monitor
Input 1
Alarm
contact
Alarm
contact
Alarm
Relay
Relay
Input
Voltage
Monitor
Input 2
Alarm
contact
Alarm
contact
Input 1
ok
Input 2
ok
Input 1
Input 2
Output
Chassis
Ground
Ground
9. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 9-1 Front side
A Output
terminals
B Chassis ground terminal
Connection of the chassis is optional and not required since the unit fulfils the
requirements according to protection class III.
requirements according to protection class III.
C Input
terminals for input 1
D Input
terminals for input 2
E Alarm-signal
terminals for input 1 monitoring (relay contact)
F Alarm-signal
terminals for input 2 monitoring (relay contact)
G Green
LED for input 1 (LED is on, when input voltage is in range)
H Green
LED for input 2 (LED is on, when input voltage is in range)
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted