Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
8.  F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 8-1   Functional diagram 
 
 
+
-
+
-
+
-
Alarm
Relay
Input
Voltage
Monitor
Input 1
Alarm
contact
Alarm
Relay
Input
Voltage
Monitor
Input 2
Alarm
contact
Input 1
ok
Input 2
ok
Input 1
Input 2
Output
Chassis
Ground
 
 
 
 
 
9.  F
RONT 
S
IDE AND 
U
SER 
E
LEMENTS
 
 
 
        Fig. 9-1   Front side 
 
 
 
 
A Output 
terminals 
 
B  Chassis ground terminal 
Connection of the chassis is optional and not required since the unit fulfils the 
requirements according to protection class III. 
 
C Input 
terminals for input 1 
 
D Input 
terminals for input 2 
 
E Alarm-signal 
terminals for input 1 monitoring (relay contact) 
 
F Alarm-signal 
terminals for input 2 monitoring (relay contact) 
 
G Green 
LED for input 1 (LED is on, when input voltage is in range) 
 
H Green 
LED for input 2 (LED is on, when input voltage is in range) 
 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
7/18