Catalyst 4500 Series Switches Installation Guide
78-14409-08
Chapter 3      Installing the Switch in a Rack
System Ground Connection Guidelines
Connecting System Ground and Power
This section describes how to connect the Catalyst 4500 series switches to earth 
ground. The system ground connection is required if FXS modules are installed 
or if this equipment is installed in a US or European Central Office.You must 
complete this procedure before connecting system power or turning on your 
switch.
To attach the grounding lug and cable to the grounding pad on your Catalyst 4500 
series switch, perform the following steps:
Step 1
Using a wire-stripping tool, remove approximately 0.75 inches (19 mm) of the 
covering from the end of the grounding wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding 
lug (
).
Step 3
Using a crimping tool, secure the grounding wire in place in the grounding lug.
Step 4
Locate the grounding pad on the switch. 
See 
 for the location of the grounding holes on the Catalyst 4503 
switch, 
 for the location on the Catalyst 4506 switch, 
 for 
the location on the Catalyst 4507R switch, and 
 for the location on the 
Catalyst 4510R switch.