AC Cable Replacement
To replace the AC cable:
Strip 1 ¾ ” of the outer jacket of the new AC power cord.
Strip 1/4” of the insulation from the end of each wire
Install the new AC power cable by reversing the steps above. Ensure that the hot,
neutral, and ground connections are connected to the appropriate screw terminals.
WARNING: Failure to connect the proper wire to the proper terminal will create a severe
safety hazard.
Most wire is color-coded, but not all manufacturers follow the same standards and not all
installations have been done properly. Typical color codes (per the US National Electrical
Code IRC E3307) are:
Ground = Green or Green/Yellow or bare
Neutral = White or Gray
Hot = Any other color (typically Black or Red)
In the US, any color other than white, green, or gray may indicate a hot wire; there are
also exceptions allowing use of tape or other markers to re-code a wire. All wiring should
be checked with a voltmeter to ensure proper connections.
Most European countries use IEC standards where blue indicates Neutral and brown,
black, or gray indicate Hot.  
Canadian standards are governed by the CEC and may use black, red, or blue for Hot.
The ground wire must be connected to the chassis ground using a double-crimped ring
terminal.  The chassis ground screw is stainless-steel and requires a lock washer.
Check your cable with an electrical tester to ensure proper connection. 
Be sure to tighten all screws.
Tighten the cable gland
Replace the AC safety shield PRIOR to restoring AC power.
WARNING: AC line voltages are hazardous and can cause shock, burns, or death.
The AC safety shield should only be removed by qualified personnel experienced with
handling high voltages.   AC power must be disconnected at the circuit breaker or fuse
box prior to making any changes to Gateway AC cabling.
Surge Suppression
Devices powered from AC supplied outside the service entrance for a building may be exposed to
significantly more and larger power surges due to lighting striking the power grid.  While no
system can protect against direct lightning strikes, the Gateway AC power supply includes
proprietary surge suppression circuitry designed to protect the gateway from hundreds of 6000V
3000A surges (ref. ANSI C62.41).
In the event of a failure, the surge suppression circuit is designed to fail open-circuit to prevent
dangerous conditions.  The power supply also includes a self-resetting fuse for over-current
protection.   Note that the self-resetting fuse does not completely disconnect AC power but only
keeps it to safe levels; AC power must be disconnected externally for safety before removing the
AC safety shield, even if power appears to be off.