 Installation and Maintenance Manual 
 
40 
5.  Type  in  the  unique  IP  address  assigned  to  the 
Manager Gateway in the Manager Gateway IP 
Address  
field.  You  will  need  to  enter  the 
appropriate  information  in  the  Manager 
Gateway Port
Manager Gateway User Name
and  Manager Gateway Password  boxes  if this 
was changed through the Admin Toolset. 
6.  To  add  a  wSIM  or  Repeater,  in  the  Essential 
Insight.mesh  Configuration  dialog  box,  select 
the Manager Gateway, and then click the 
 
detect nodes button. 
7. 
Click  OK.  The  Essential  Insight.mesh  device  is 
added to the Instrument Hierarchy. 
8. 
Save the Enterprise. 
6.2  Data collection considerations 
A wSIM collects one type of data (static or dynamic) 
for one channel at one time. So, for all four channels, 
it  takes 8 different “collections”  at different  times.  In 
between  each  collection,  the  node  has  to  “re-
charge”.  This  recharge  time  varies  depending  on 
wSIM  temperature  and  channel  configuration 
parameters. 
So, in order to not conflict with other schedule times, 
dynamic data needs to be scheduled in between the 
static  data  collection  times.  Static  data  collection  is 
offset from midnight. So a 2 hour collection rate will 
attempt  to  collect  data  on  the  even  hours  (0000, 
0200, 0400, 0600, … 2200) in the day.  
We  recommend  that  dynamic  data  be  on  the  odd 
hours  of  the  day,  if  you  have  a  2-hour  static 
collection interval. 
Assume  a  re-charge  time  of  approximately  15 
minutes  between  measurements.  For  collecting 
static data every 2 hours the data collection cycle is