Bently Nevada Inc. 18531001 Benutzerhandbuch

Seite von 58
Section 6 -  Configuring Essential Insight.mesh 
 
41 
Collect Channel 1 static… 
Re-charge 
Collect Channel 2 static… 
Re-charge 
Collect Channel 3 static… 
Re-charge 
Collect Channel 4 static… 
Re-charge 
With  the  assumption  that  the  re-charge  time  is 
approximately  15  minutes,  you  can  see  that  with  a 
scheduled  collection  time  of  2  hours,  the  time 
difference from the first to the last channel could be 
45 minutes. 
Further,  transducer  type,  integration,  low  frequency 
high  pass  filter  corners,  and  high  resolution 
waveforms will result in longer collection periods that 
consume more power and result in the battery taking 
longer  to  recharge.  If  more  power  is  consumed  it 
takes  more  time  to  recharge  before  the  next 
measurement can be made. 
15  min  static  sample  interval  should  be  used  as  a 
temporary,  bad  actor  analysis  tool.      Only  one 
channel should be set to static data every 15 min to 
reduce delayed data collection on other channels. 
High-resolution waveforms should only be used as a 
temporary, analysis tool during trouble shooting.  For 
example,  when  a specific  bearing  defect  is  trying to 
be identified. 
The recommended configuration is: 
Channel 1 Static - 2 hours 
Channel 2 Static - 2 hours