Andrew Wireless System CAPL17E19 Benutzerhandbuch
ION®-E Series Low Power Carrier Access Point Installation Guide
M0201AAC
Page 40
© February 2018 CommScope, Inc.
Installing CAP Ls
7
Connect the Vdc Power connector as appropriate for this installation.
•
For a CAP L with no local power supply and no hybrid fiber cable, connect a power cable (not supplied
by CommScope) to the proprietary 4-pin, 36 to 60 Vdc Power connector on the CAP L.
by CommScope) to the proprietary 4-pin, 36 to 60 Vdc Power connector on the CAP L.
•
For a CAP L powered by the CAP L Hybrid Fiber Splice Box Kit (PN 7774354-xx) connect the:
–
–
power cable the proprietary 4-pin, 36 to 60 Vdc Power connector on the CAP L, and terminate the
other end to the CAP L Hybrid Fiber Splice Box
other end to the CAP L Hybrid Fiber Splice Box
–
LC Fiber Jumper to the supplied OCTIS connector, and splice the other end of the fiber jumpers
inside the locally-mounted CAP L Hybrid Fiber Splice Box.
inside the locally-mounted CAP L Hybrid Fiber Splice Box.
•
For a CAP L with the optional AC/DC Power Supply Kit (PN 7775087-xx), connect its Local Power
Jumper Cable Assembly to the proprietary 4-pin, 36 to 60 Vdc Power connector on the CAP L.
Jumper Cable Assembly to the proprietary 4-pin, 36 to 60 Vdc Power connector on the CAP L.
Cable a CAP L with a Copper Interface
All installations of a CAP L with a Copper Interface must follow the rules in
. Follow the cabling instructions that apply to the unit type that
you are installing.
•
•
Cat6A Cable Requirements for CAP Ls with a Copper Interface
The following cabling rules must be observed for all installations of a CAP L with a Copper Interface.
•
Plenum rated cable must be used wherever it is required by local electrical codes.
•
Shielded twisted pair is not required unless operating in a high RFI/EMI environment.
•
An ION-E system requires a minimum Signal-to-Noise Ratio (SNR) of 25 dB, and Alien Crosstalk (AXT)
must not degrade SNR on any cable by more than 0.5dB.
must not degrade SNR on any cable by more than 0.5dB.
•
Cat6A cable wire size requirements are as follows:
–
–
23 AWG Cat6A cable (minimum EIA/TIA standards) must be used between RJ-45 connector points
–
24 AWG is the minimum wire size allowed for a Cat6A Patch Cord.
•
CommScope strongly recommends using factory terminated and tested Cat6A Patch Cord.
For information on how to test your Cat6A cables and connections, see
.