3.4.4 
MAC payload for standard commissioning telegrams 
 
Figure 9 below shows the MAC payload structure of a standard commissioning telegram. 
 
 
 
 
 
Figure 9: MAC Payload structure for standard commissioning telegrams 
 
The following fields are used for standard commissioning telegrams: 
 
 
Telegram Control (1 byte) 
 
The Telegram Control field is set to 0x0C to identify a standard telegram (secure com-
munication will be established based on the commissioning telegram) 
 
 
Source ID (4 bytes) 
 
The Source ID field contains a 4 byte ID uniquely identifying each PTM 535Z device 
 
 
Commissioning Command (1 byte) 
The Commissioning Command field is set to 0xE0 by PTM 535Z 
 
 
Device Type (1 byte) 
The Device Type field is set to 0x02 by PTM 535Z 
 
 
Device Options (1 byte) 
The Device Options field is set to 0x01 by PTM 535Z