Honeywell International Inc. WFSLCDUI Benutzerhandbuch

Seite von 96
PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013  
23
Configuration and Programming
W-GATE
Mesh Formation with PC Tools
To create a mesh network using the PC Tools, perform the following steps.
1.
Connect the W-USB dongle device to your computer. For more information on USB dongle, 
refer to Section 5:, "USB Adapter".
2.
Launch the PC tools application.  Refer to Appendix B:, "PC tools" to know about launching 
the PC tools application.
3.
Go to Create Mesh Network step.
4.
Navigate to the second step of Create Mesh Network by clicking  
 
on top of the screen.
5.
Click to select the W-GATE displayed in the Gateways in Range table, and click 'Start Mesh 
Formation
'.
When the mesh is formed, the tool helps you to track the number of devices that have joined the 
mesh, and view the progress. The mesh formation terminates 10 minutes after the last device joins 
the mesh.  In addition, it can be terminated by the user by clicking Stop Mesh Formation.
Once mesh formation is complete, the network transitions to optimize the mesh. For further operat-
ing instructions, refer to 2.7, "Operations".
2.6.3  Profile Distribution
There are two ways to initiate profile distribution from the W-GATE.  
Automatically after creating a profile, 
Activating the profile creating magnetic sensor when it has a profile.  
After Creating a Profile  
Profile distribution is automatically enabled from the W-GATE after creating a profile.  The profile 
distribution automatically terminates after 10 minutes. 
Activating the Profile Magnetic Sensor When it has a Profile  
Activating the profile magnetic sensor while it 
has profile will put the W-GATE in a mode of 
distributing the profile to any device that 
requests a profile. The W-GATE’s LED pattern 
will be altered when it is distributing a profile 
for easy identification.  Profile distribution will 
automatically terminate after 10 minutes. For 
more information on W-GATE LED patterns, 
refer to the table in 2.7.3, "LED Indications". 
Figure 2.9   Profile Magnetic
Sensor on a W-GATE