PRELIMINARY: Firelite Wireless Sensor Network P/N LS10036-000FL-E:N0 10/10/2013
Wireless Display Driver (W-DIS-D)
ANN-80 Operations
3.9 ANN-80 Operations
The ANN-80 displays wireless specific events for the associated mesh network. Alarm conditions
and trouble events that are displayed by the FACP are not displayed at the ANN-80. The ANN-80
incorporates an automatic resound of the piezo and trouble indicator every 4 hours for active
events.
and trouble events that are displayed by the FACP are not displayed at the ANN-80. The ANN-80
incorporates an automatic resound of the piezo and trouble indicator every 4 hours for active
events.
3.9.1 Buttons and Switches
The buttons and switches in the ANN-80 are displayed below in the image and are explained in the
Table 3.5 .
Table 3.5 .
Figure 3.6 Buttons in ANN-80
Table 3.5
Button
Action
Drill button
Not Used
Up Arrow
Press the UP Arrow to scroll up
through the messages
through the messages
Ack button
Press the ACK button to
acknowledge the messages
acknowledge the messages
Down Arrow
Press the Down Arrow to scroll
down through the messages
down through the messages
Silence button
Not Used
Reset button
Press the Reset button
to clear latching wireless
events
to clear latching wireless
events
Key switch
Use the Key switch to switch on
and switch off, to enable the
Reset button
and switch off, to enable the
Reset button