Xsilogy Inc. 0920HP Benutzerhandbuch
Appendix B – IEEE Recommended Battery Maintenance Programs
Appendices
Annual Augmentation of Quarterly Inspections –
Check and Record:
Check and Record:
a. Specific gravity of each cell
b. Cell condition (detailed visual inspection of each cell in contrast
to the general monthly inspection)
c. Cell-to-cell and terminal connection detail resistance
d. Structural integrity of the battery rack and/or cabinet
Valve-Regulated Lead-Acid (VRLA) Batteries
for Stationary Applications
(IEEE STD 1188-1996)
for Stationary Applications
(IEEE STD 1188-1996)
Monthly Inspection – Check and Record:
a. Overall float voltage measured at the battery terminals
b. Charger output current and voltage
c. Ambient temperature and the condition of ventilation and
monitoring equipment
d. Visual individual cell/unit condition to include:
1. Cell/unit integrity for evidence of corrosion at terminals,
connections, racks or cabinet
2. General appearance and cleanliness of the battery, the
battery rack or cabinet and battery area, including
accessibility
accessibility
3. Cover integrity and check for cracks in cell/unit or
leakage at electrolyte
4. Excessive jar/cover distortion
Quarterly Augmentation of Monthly Inspections –
Check and Record:
Check and Record:
a. Cell/unit internal ohmic values
6-6