Xsilogy Inc. 0920HP Benutzerhandbuch

Seite von 46
Appendices 
Appendix B – IEEE Recommended Battery Maintenance Programs 
b.  Temperature of the negative terminal of each cell/unit of the 
battery 
c.  For applications with a discharge rate of 1 hour or less, a 
representative sample of the intercell connection detail resistances 
(minimum 10% or six connections). If an upward trend is detected 
from the initial readings, measure all connection resistances, 
determine the cause, and take corrective action as needed. Test 
different connections each quarter. 
Semiannual Augmentation of Monthly Inspections 
– Check and Record: 
a.  Voltage of each cell/unit 
Yearly Augmentation of Monthly Inspections – 
Check and Record: 
a.  Cell-to-cell and terminal connection detail resistance of entire 
battery 
b.  AC ripple current and/or voltage imposed on the battery 
 
 
Preliminary Release X1 
6-7