Xsilogy Inc. 0920HP Benutzerhandbuch
Appendices
Appendix B – IEEE Recommended Battery Maintenance Programs
b. Temperature of the negative terminal of each cell/unit of the
battery
c. For applications with a discharge rate of 1 hour or less, a
representative sample of the intercell connection detail resistances
(minimum 10% or six connections). If an upward trend is detected
from the initial readings, measure all connection resistances,
determine the cause, and take corrective action as needed. Test
different connections each quarter.
(minimum 10% or six connections). If an upward trend is detected
from the initial readings, measure all connection resistances,
determine the cause, and take corrective action as needed. Test
different connections each quarter.
Semiannual Augmentation of Monthly Inspections
– Check and Record:
– Check and Record:
a. Voltage of each cell/unit
Yearly Augmentation of Monthly Inspections –
Check and Record:
Check and Record:
a. Cell-to-cell and terminal connection detail resistance of entire
battery
b. AC ripple current and/or voltage imposed on the battery
Preliminary Release X1