System Installation Guide
18
69-2688—01  I/O-CHTSTAT03
Status (STATUS)
Sub-menu Item
Indication (for Display Only; not User Modifiable)
Mode (MODE)
Displays the current air handler operating mode
CFM (CFM)
Displays the airflow for the current operating mode
Cool Set-up (SETUP)
Sub-menu
Item User Modifiable 
Options
Comments
Cool Airflow Trim 
(CL TRM)
-10% to +10% in 2% 
Increments (Default 0%)
Selects the airflow trim amount; applies to air 
conditioner only.
Cool Airflow Profile 
(CL PRFL)
A, B, C, or D (Default D)
Selects the airflow profile; applies to air 
conditioner only.
Cool ON Delay (CL 
ON)
5, 10, 20, or 30 seconds 
(Default 5)
Selects the indoor blower on delay; applies to 
air conditioner only.
Cool OFF Delay (CL 
OFF)
30, 60, 90, or 120 
seconds (Default 30)
Selects the indoor blower off delay; applies to 
air conditioner only.
Dehumidification 
Select (DEHUM)
ON or OFF (Default is 
OFF)
Selecting “OFF” disables dehumidification; 
selecting “ON” enables dehumidification; 
applies to air conditioner only.
Heat Set-Up (HT SETUP) Applies to Heat Pump Systems Only
Sub-menu Item User Modifiable Options
Comments
Heat Airflow Trim 
(HT TRM)
-10% to +10% in 2% 
Increments (Default 0%)
Selects the airflow trim amount; applies to heat 
pump only.
Heat ON Delay 
(HT ON)
5, 10, or 15 seconds 
(Default 5-sec.)
Selects the indoor blower on delay; applies to 
heat pump only.
Heat OFF Delay 
(HT OFF)
30, 50, 70, or 90 seconds 
(Default 30-sec.)
Selects the indoor blower off delay; applies to 
heat pump only.
Defrost Interval 
(DEFROST)
30, 60, 90, or 120 minutes 
(Default 30-min.)
Selects the time interval between defrost; 
applies to heat pump only.
Compressor 
Delay (CMP DLY)
0, 5, 15, or 30 seconds 
(Default 30-sec.)
Selects the compressor off time after a 
reversing valve shift; applies to heat pump only.