Skyroute CL3050  Standalone Wireless Communicator
10
[02]
Mode 2 - (2) 24-Hour Zones
In this mode, both the YEL and 
GRN terminals on the Skyroute 
CL3050 will be used as zone 
inputs.  These zones will support 
the DSC standard EOL configura-
tion and loop response.  Pro-
gramming sections will allow the 
installer to change the default 
zone types and attributes. The 
Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central sta-
tion.
[03]
Mode 3 - (8) 24-Hour Zones
In this mode, the Skyroute 
CL3050 is connected to a 
PC5108 zone expander using 
the corresponding RED, BLK, 
YEL and GRN terminals.  The 
Skyroute CL3050 will drive the 
Keybus to communicate with 
the PC5108.  A +12V
DC
 sup-
ply connected to the RED and 
BLK terminals is required 
when using this mode. The Programming sections will allow the installer to 
change the default zone types and attributes.  The Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central     
station.
Note: This configuration can not be used with an AC supply.
Note: Jumpers on the PC5108 must be set as follows:
J1
J2
J3
ON
OFF
ON
J4
J5
J6
OFF
OFF
ON
Default - [01 -03]  dependant on start up configuration
[11] Skyroute CL3050 Configuration Options 1
Option 1 - A Channel Selected/ B Channel Selected. 
All Modes
This Option determines whether cellular channel “B” or channel “A” is used. In 
Canada, Channel B is used (Default). In the USA refer to the SID list for the chan-
nel of the cellular service provider in your area. Default - Channel B
Option 2 - Normally Closed Loops/ End-of-line Resistors                Mode 2, 3
Normally Closed Loops can be wired as shown. Multiple 
Normally Closed contacts can be wired in series. For Double 
or Single EOL resistors this option must be set to OFF
Default - Normally Closed (N/C) Loops.
Option 3 - Double EOL Resistors/Single EOL Resistors
Mode 2, 3
This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired 
as indicated
Input Voltage
9-12V
 or V
AC
DC
Zone 1 Input
Zone 2 Input
Zone Common
Trouble Output
RED    BLK   YEL  GRN  COM  PGM
To Keybus
Connections
on PC5108
System Common
Trouble Output
RED    BLK   YEL  GRN  COM  PGM