ADC Telecommunications Inc. FWM1901B Benutzerhandbuch

Seite von 36
ADCP-75-246 • Issue 1 • 6/2008
Page 23
© 2008, ADC Telecommunications, Inc.
6.6
AC Power Wiring Installation
A 15-foot connectorized 3-wire cable (also available in lengths of 40, 60, or 100 feet) is provided
for the AC power connections. The connectorized end of the cable connects to the AC power port
located on the bottom of the enclosure. The stub end of the cable must be routed to an external
junction box (not provided) for permanent connection to the AC power system wiring. 
The AC power source must supply 120 or 240 VAC, 50 or 60 Hz, single-phase power through a
15 Amp circuit breaker. The AC power cable provides three wire leads for line, neutral, and
ground connections. The power cable is rated for indoor or outdoor use and must not be placed
within electrical conduit as this will impede the cooling of the cable during usage. The electrical
junction box and any conduit, wire, and fittings required must be provided by the installer. 
Use the following procedure to install the AC power wiring:
1. Locate the AC power cable that is provided separately with the enclosure.
2. Route the power cable between the AC power port, located on the underside of the
enclosure and the nearest AC power junction box as shown in 
. It may be
necessary to install a new junction box if an existing junction box is not available. 
Figure 14.  Typical AC Power Cable Routing
Note: It is recommended that an AC outlet be installed near the enclosure for powering
tools and test equipment. This outlet must include a GFCI device for protection. 
Note:  All electrical work must comply with local codes and requirements. A locally
licensed electrical contractor is best qualified to perform this work. For additional
information, consult with the ADC Technical Assistance Center.
Danger: Use extreme caution when working with high voltage AC power. Ensure all power is
disconnected before working on power circuits.
microBTS
ENCLOSURE
22087-A
AC POWER 
JUNCTION BOX 
AC POWER 
CABLE 
AC POWER 
WIRES ROUTED 
TO CIRCUIT 
BREAKER PANEL