7000 Series Keypad Installation Sheet
6
7000 Series Keypad Installation Sheet 
Digital Monitoring Products
7
Installer Options Menu
The 7000 Series keypads also contain Keypad Option and Keypad Diagnostic programs that allow installers and 
service technicians to configure and test keypad operation.
Access the User Menu
Access the Installer Options Menu through the User Options function.  Hold down the <— and CMD keys for a few 
seconds to display the SET BRIGHTNESS prompt.  Immediately enter the code 3577 (INST) and press CMD.  The 
display changes to KPD OPT (keypad options) KPD DIAG (keypad diagnostics) and STOP.
The keypad options menu allows you to set the keypad address, select supervised or unsupervised mode, change 
the default keypad message, individually arm the 2-button Panic keys, and select Soft-Shunt, Request-to-Exit, and 
4-digit entry cards. 
Programming Keypad Options
KPD  KPD
OPT  DIAG 
  STOP
  Keypad Options (KPD OPT) 
To program keypad options, press the left Select key under KPD OPT.  The display 
changes to CURRENT KEYPAD ADDRESS:  # #. 
CURRENT KEYPAD
ADDRESS:    01
  Keypad Address
Set the keypad address from 01 to 05 with the XRSuper6 and XR20, from 01 to 08 
with the XR40, XR200, XR2400F, and 01 to 16 with the XR200-485, XR500 Series, and 
XR2500F.  The factory default address is set at 01.  To change the current address, press 
any Select key and then enter the new address using the appropriate number keys on 
the keyboard.  It is not necessary to enter a leading zero for addresses 01 to 09.
KEYPAD MODE:
*SUP 
 
 UNSUP
  Keypad Mode
Configure the keypad for either supervised or unsupervised operation.  You have the 
option to supervise keypads with zones connected to them.  Supervised keypads cannot 
share addresses with other keypads.  To enhance the supervision feature, assign an 
output to the Device Fail Output in panel programming and connect a device to the 
corresponding output that trips when the keypad fails.  This provides notification at the 
central station and the site.  The other keypads do not display the device fail. 
Unsupervised keypads can operate with other unsupervised keypads sharing the same 
address.  Zones cannot be used on unsupervised keypads.  To change the current 
setting, press the Select key under SUP or UNSUP.  An asterisk appears next to the 
selected option.
Note: An unsupervised address cannot be programmed for Device Fail Output. 
DEFAULT KEYPAD MSG:   Default Keypad Message
Enter a custom message of up to 16 characters to appear on the keypad display top line 
whenever that line is not used for any other purpose.  Press any Select key to clear the 
current display and use the data entry keys to enter a new custom display. 
ARM PANIC KEYS:
*PN  *EM  *F1
  Arm Panic Keys
Use this option to configure the top row Select keys as 2-button Panic keys.  To enable 
or disable a Panic, press the Select key under the appropriate display: PN (Panic), EM 
(Emergency), and FI (Fire).  Once the panic is enabled, an asterisk displays next to the 
description.  Refer to the Panic Key Options section earlier in this document.
7/0 PANIC 
ENABLE:    NO  YES
  7/0 Panic
Use this option to configure the 7 and 0 keys as a 2-button Panic feature.  To enable 
the 7/0 Panic, select YES.  To disable the option, select NO.  Default is NO.  In a panic 
situation simply press and hold the 7 and 0 keys for two seconds.  Refer to the Panic 
Key Options section earlier in this document.
ACTIVATE ZONE 2
SHUNT: 
  NO  YES
  Zone 2 Shunt (7075 only)
Select YES to enable the Soft-Shunt™ option on zone 2. This zone provides the 
Soft-Shunt™ for door contacts. Zone 2 must be programmed into the panel.