Honeywell International Inc. 8DL5809EN Benutzerhandbuch
¬.?l
K9948 4/04 Rev. A
1. Surface mount the unit’s plastic base to a wall or
ceiling, or mount the plastic base to either a 4” junction
box or 3-1/4 octagon box.
box or 3-1/4 octagon box.
NOTE: The anti-twist mounting hole is for use when
installing the device directly to wall-board to prevent
the base from being twisted off when servicing the
device.
installing the device directly to wall-board to prevent
the base from being twisted off when servicing the
device.
2. Install the detector assembly to the base and secure by
twisting clockwise. Make sure to align the tamper
posts in the base with the tamper index relief’s in the
detector assembly.
posts in the base with the tamper index relief’s in the
detector assembly.
MOUNTING
HOLES
5809EN-002-V0
TAMPER
POSTS
ANTI-TWIST
MOUNTING HOLE
TESTING THE DETECTOR
The test procedure should be performed to determine a good
RF transmission path and again after installation is
completed.
RF transmission path and again after installation is
completed.
CAUTION: The rate-of-rise heat sensor is intended for one-
time use. Prolonged heat during testing can
damage the unit. If used carefully following
the instructions described below, the heat from
a portable hair dryer can be used to test the
unit. If the round disk on top of the detector
detaches, the detector must be replaced.
damage the unit. If used carefully following
the instructions described below, the heat from
a portable hair dryer can be used to test the
unit. If the round disk on top of the detector
detaches, the detector must be replaced.
Activate the control panel’s test mode.
Use either method (a) or (b) to activate the detector:
(A) Press and release the activation button on the PC
board assembly.
OR
(B) Holding a portable hair dryer about 12 to 18 inches
away from the detector, turn the dryer on and aim
the warm air at the side of the detector.
the warm air at the side of the detector.
CAUTION: Aiming the dryer directly at the round disk on
the detector can damage the detector requiring
the unit to be replaced.
the unit to be replaced.
The system’s keypads should beep and the detectors ID
should be displayed.
should be displayed.
Exit the control’s test mode.
MAINTAINING PROPER OPERATION
To maintain the detector in proper working condition, it is
important that you observe the following:
important that you observe the following:
Replace the battery when the system indicates that the
5809EN has reported a low battery condition.
5809EN has reported a low battery condition.
Units should never be relocated without the advice or
assistance of the alarm service company.
assistance of the alarm service company.
SPECIFICATIONS
Power: 3V lithium battery
(Duracell DL123A, Panasonic CR123A, Sanyo CR123A,
Varta CR123A)
(Duracell DL123A, Panasonic CR123A, Sanyo CR123A,
Varta CR123A)
CAUTION: Risk of fire, explosion, and burns. Do not
recharge, disassemble, heat above 212
°F
(100
°C) or incinerate. Dispose of used batteries
promptly. Keep away from children.
Operating Temperature:
40
° to 140°F (6° to 60°C)
Rate-of-Rise Temperature: 15
°F (8°C) increase per minute
NOTE: Rate of rise sensor
does not operate above 38
does not operate above 38
°C)
Fixed Temperature:
135
°F (57°C)
Maximum Spacing:
50ft x 50ft UL
30ft x 30ft FM
(refer to National Fire Alarm
Code Standard NFPA 72 for
application requirements)
(refer to National Fire Alarm
Code Standard NFPA 72 for
application requirements)
Dimensions:
4.4” diameter/ 2/2” deep
TO THE INSTALLER
The rate-of-rise mechanism may be subject to reduce sensitivity
over time. Annual testing of the rate-of-rise operation is
recommended.
over time. Annual testing of the rate-of-rise operation is
recommended.
Regular maintenance and inspection (at least annually) by the
installer and frequent testing by the user are vital to continuous
satisfactory operation of any alarm system.
installer and frequent testing by the user are vital to continuous
satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and
offering a regular maintenance program to the user as well as
acquainting the user with the proper operation and limitations of
the alarm system and its components parts. Recommendations
must be included for specific program of frequent testing (at least
weekly) to ensure the system’s proper operation at all times.
offering a regular maintenance program to the user as well as
acquainting the user with the proper operation and limitations of
the alarm system and its components parts. Recommendations
must be included for specific program of frequent testing (at least
weekly) to ensure the system’s proper operation at all times.
FCC NOTICE
FCC ID: CFS8DL5809EN
This device complies with Part 15 of FCC rules. Operation is
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
CANADA: 1748A-5809EN
REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE
CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR
WARRANTY INFORMATION AND LIMITATIONS OF THE
ENTIRE ALARM SYSTEM.
CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR
WARRANTY INFORMATION AND LIMITATIONS OF THE
ENTIRE ALARM SYSTEM.
C
US
R
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International Inc.
www.honeywell.com/security