Nokia of America Corporation BBTRX-22 Benutzerhandbuch

Seite von 141
Grounding and surge protection requirements
Grounding requirements
WARNING
Electric-shock hazard
There is a danger of electric shock if the grounding system is inadequate.
You must comply with the grounding requirements for the grounding system.
The installation site must be grounded with an integrated (multi-point) grounding system.
The equipment is susceptible to lightning surges due to its association with towers and
antennas. Therefore, it is imperative that the site be properly grounded and that a low
impedance path to earth (10 ohms or less) is provided. The grounding conductors must be
as straight and short as possible. No sharp bends or loops are permitted in grounding
conductors.
Refer to Grounding and Lightning Protection Guidelines for Alcatel-Lucent Network
Wireless System Cell Sites, 
401-200-115, for detailed grounding requirements.
Note: The figures included below show typical grounding schemes. However, for
detailed requirements, refer to document 401-200-115
The equipment warranty can be voided if the guidelines detailed in the National Electric
Code (NFPA 70), the Canadian Electrical Code, Part I (CSA C22.1), or the local electrical
code in effect, as well as the Standard for Installation of Lightning Protection Systems,
NFPA 780, and document 401-200-115 are not followed.
Important! All grounding system material (cable, connectors, buses, and so forth)
must be of high quality materials that resist deterioration and require little or no
maintenance.
Grounding requirements
Grounding and surge protection requirements
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
5-2
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements
B25 RRH4x30
3MN-02023-0001-RJZZA
Issue 0.02
January 2015