Grounding for pole mount configuration
When a Alcatel-Lucent B25 RRH4x30 is mounted to a pole, the site must provide a
ground wire for the B25 RRH4x30. The pole must also be adequately grounded as
needed. For outdoor applications #2 AWG wire is required and for indoor applications
#6 AWG wire is required.
Note: Ground lugs are provided with the ground lug kit (part number 301022679) and
#2 AWG ground wire, C-tap, and hardware are provided in the RRH outdoor
grounding kit (part number 301080628).
The following figure shows an example of pole mount grounding.
2 AWG to 2 AWG
To antenna
ground
To antenna
ground
35 mm
(2 AWG)
2
35 mm
(2 AWG)
2
To system grounding
electrode or ground rod
2 AWG to 2 AWG
35 mm
(2 AWG)
2
Grounding requirements
Outdoor grounding system
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
5-4
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements
B25 RRH4x30
3MN-02023-0001-RJZZA
Issue 0.02
January 2015
D
R
AFT
D
R
AFT