2600T Series Pressure transmitters | OI/266/WIHART-EN   23
5 Mounting
5.13.3 Liquid level measurements on closed tanks and 
non condensable fluids (dry leg)
  — Mount the transmitter at the same height or below the    
    lowest level to be measured.
  — Connect the + (H) side of the transmitter to the bottom of  
    the tank.
  — Connect the - (L) side of the transmitter to the upper part  
    of the tank, above the maximum level of the tank.
5.13.4 Liquid level measurement with closed tanks and 
condensable fluids (wet leg)
 — 
Mount the transmitter at the same height or below the    
    lowest level to be measured.
 — 
Connect the + (H) side of the transmitter to the bottom of  
    the tank.
 — 
Connect the - (L) side of the transmitter to the upper part  
    of the tank.
 — 
Fill the vertical section of the connecting line to the upper  
    part of the tank with a compatible liquid through the  
 
    dedicated filling tee.
Figure 24: Level measurement on closed tank with dry leg
Figure 25: Level measurement on closed tank with wet leg
5.13.5 Liquid level measurement with open tanks
  — Mount the transmitter at the same height or below the    
    lowest level to be measured.
  — Connect the + (H) side to the bottom of the tank.
 — 
Vent the “–” (L) side of the transmitter to the atmosphere  
    (in this case a gauge pressure is shown; the (L) side is    
    already vented to the atmosphere).
Figure 26: Level measurement on open tank with P style transmitter