ABB WICB Benutzerhandbuch

Seite von 72
30   OI/266/WIHART-EN | 2600T Series Pressure transmitters
7 Commissioning
7.7.2 Burst status
The device supports up to three Burst communications. Each 
burst can be individually configured and enabled (ON) or 
disabled (OFF). Depending on its configuration, each Burst 
communication can have different possible Status that could be 
helpful for detecting and evaluating possible critical or 
anomalous situations between the gateway and the wireless 
devices. If read from the wireless devices, some Burst Status 
could give information about the wrong configuration of the 
gateway and/or the wireless device installed. Burst status is 
readible via HMI (if installed) or via dedicated section of the DTM 
(see Commissioning by DTM).
Burst status have the following structure:
“Bn: X-Y” where:
  — Bn is the Burst number as B1, B2 or B3 
  — X-Y represent two possible channels in negotiation with    
    the Network Manager (Gateway) for each Burst. These    
    letters can assume different values:
  “O” =  OFF 
     
the associated burst has not been enabled.
     
If the device has joined the network bursts can be    
     
enabled wirelessly, through wired DTM or using an    
     
handheld terminal. In case the device has not yet  
 
     
joined, burst enabling can be done through the wires   
     
of the HART protocol or exploiting the DD file  
 
     
(handheld terminal)
  “N” =  Negotiating phase 
     
the associated burst is in the negotiation phase with   
     
network manager (gateway) that is reserving the  
 
     
correct resources bandwidth, timings, etc.
  “R” =  Reject
     
the associated burst setting has been refused by the   
     
network manager due to some possible conflicts i.e:   
     
bandwidth limitation or requested burst update period  
     
too short. In case this value appears, review the  
 
     
update period.
Figure 34: Burst B2 in OFF-OFF status
Figure 33: Burst visualization into DTM
  “S” =  Shutdown 
     
the associated burst is in the shutdown phase. The    
     
network manager is deleting all the resources  
 
     
previously reserved at this burst. Until the burst is in    
     
this condition, it cannot be reconfigured.
  “A” =  Active 
     
the associated burst is Active/running,In this condition  
     
the associated Burst is transmitting the selected  
 
     
HART command or status to the Gateway according   
     
to the update period.
The Bursts will be OK only when X-Y are displayed with 
“A” - “A” or “A” - “O”.
When the selected “Burst Trigger” is set to “Continuous” there 
is only one channel to be negotiated with the Network Manager 
and in this case the second letter is not relevant (value fixed to 
“O” - OFF). When the selected “Burst Trigger” is set to any 
other event (Window, Rising, Falling or On-change), there are 
two channels to be negotiated with the Network manager i.e. 
one for the selected trigger event and the second for the 
Maximum Update Period in case the trigger event never 
occurs. In this case the X-Y represents the two channels. The 
three bursts are displayed cyclically with an interval of 10 
seconds. 
7.7.3 Status byte
The Status byte is the fifth byte of any out value and represents 
the Quality of the variable. Depending by which of the two 
selections is active, the list of the possible Status can be the 
following:
  — Classic Status
Binary 
Code
Decimal 
Code
Meaning
Possible Cause
0x08
8
More Device 
Status Available
E.g. faluire state. 
Additional status command shall be 
sent for more details.
0x40
64
Poor accuracy
E.g. value is beyond rated pressure,  
temperature outside range.
Additional status command shall be 
sent for more details.
0xB0
176
Manaul / Fixed
E.g. simulad value or forced.
Additional status command shall be 
sent for more details.
0xC0
192
Good
Out of Service