2600T Series Pressure transmitters | OI/266/WIHART-EN   31
7 Commissioning
7.8 Commissioning by EDD-based HART Handheld 
Terminal
The handheld terminal will allow you to set all the relevant 
information to let the 266 WiPressure join a WirelessHART 
network.
  — Ensure the EDD has been loaded into the HART handheld  
   terminal.
  — Connect the HART handheld configurator to the  
 
    instrument via the HART maintenance port.
  — Set the handheld terminal to polling (multidrop) mode and  
    scan for devices. The 266 WiPressure has a default polling  
    address 1 (has per HART specification).
  — Once connected you can edit the parameters and  
 
    configuration data.
Important An EDD describes structure and type of device 
parameters but as only a limited influence on how this 
information is provided to the user. The following is an 
example of how the EDD could be represented. Even the 
parameter names may be slightly different as tools typically 
use vendor specific libraries.