7 Commissioning
7.8 Commissioning by EDD-based HART Handheld
Terminal
The handheld terminal will allow you to set all the relevant
information to let the 266 WiPressure join a WirelessHART
network.
information to let the 266 WiPressure join a WirelessHART
network.
— Ensure the EDD has been loaded into the HART handheld
terminal.
terminal.
— Connect the HART handheld configurator to the
instrument via the HART maintenance port.
— Set the handheld terminal to polling (multidrop) mode and
scan for devices. The 266 WiPressure has a default polling
address 1 (has per HART specification).
scan for devices. The 266 WiPressure has a default polling
address 1 (has per HART specification).
— Once connected you can edit the parameters and
configuration data.
Important An EDD describes structure and type of device
parameters but as only a limited influence on how this
information is provided to the user. The following is an
example of how the EDD could be represented. Even the
parameter names may be slightly different as tools typically
use vendor specific libraries.
parameters but as only a limited influence on how this
information is provided to the user. The following is an
example of how the EDD could be represented. Even the
parameter names may be slightly different as tools typically
use vendor specific libraries.