58   OI/266/WIHART-EN | 2600T Series Pressure transmitters
9 Troubleshooting
9.4 HMI as diagnostic indicator  
While the HMI works as Variable Indicator, also diagnostic 
strings can be displayed. Whenever a failure or warning 
condition is detected within the transmitter, a message appears 
in the low side of the display below the bar-graph. The 
message is formed by the NAMUR NE107 icon and the string 
of the component where the problem occurred.
NAMUR 
icons
Description
Error / Failure
Functional check (e.g. during simulation )
Out of Spec (e.g. Sensor temperature outside the specs limits)
Maintenance required
Figure 42: Example of “Maintenance / Sensor” and “Failure / 
Electronics” diagnostic
Detailed diagnostic info from HMI
When the above kind of diagnostic information is displayed, 
from the HMI it is also possible to see the details.
 1. 
Press the center navigation keys for 4 seconds until two    
    special icons appear on the bottom corners of the display 
Important. This step is necessary only for the keypad activation of 
TTG HMI type. For conventional HMI start from step 2.
 2. 
Press the left navigation key 
 3. 
The HMI enter in the special menu with three items:
     Diagnostics
     
Operator View 1
     
Signals View
 4. 
Select “Diagnostics” and the list of all the active error  
 
    conditions appears with on top the worst condition. 
The format of how the detailed diagnostic info are displayed is 
“XA.BBB” where:
X = NAMUR NE107 
Categories
A = Priority. 
(Higher number = 
higher priority)
BBB = error 
code
F = Failure
M = Maintenance
O = Out of Specification
C = Function Check
9.5 HMI as feedback of the local push button 
operations
As consequence of the operations described in the section 8.2, 
when the Z or S buttons are released, the feedback of the 
executed operation is displayed in the bottom of the LCD 
(same position as per diagnostic messages):
Message
Description
! Oper Done
The push button operation has been successfully executed
! Proc Too 
Low
The Pressure measured in input is too low and not 
acceptable for the requested operation
! Proc Too 
High
The Pressure measured in input is too high and not 
acceptable for the requested operation
! New URV 
Error
The Zero (Z) operation cannot be accepted because the 
URV would be shifted outside the Upper Sensor limit
! Span Error
The Span (S) operation cannot be accepted because the 
new URV would be too close to the LRV and their 
difference lower than the Minimum Span value 
! Oper 
Disabled
 
The push button operation has been refused because the 
Write Protection is enabled.
! LRV Too 
Low
New LRV is too low and not acceptable for the requested 
operation
LRV Too 
High
New LRV is high low and not acceptable for the requested 
operation
URV Too 
Low
New URV is too low and not acceptable for the requested 
operation
URV Too 
High
New URV is high low and not acceptable for the requested 
operation
Armed
 Device is armed to accept HART command 73 “Find 
Device”. This message can be triggered only during the 
device wakeup operation
Possible sources of error are: ELECTRONICS, SENSOR, 
PROCESS and CONFIGURATION. These sources can show up 
the above listed icons according to the specific case.