X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
The LVD tab is the set up and control for the system low voltage disconnect 
contactors.  The controller can control up to two contactors, but in X75 only LVD 
1 is installed.
The controls are as follows:
LVD 1 will open at.  This is the system voltage which will cause the controller 
open LVD 1.  Typically this is used to disconnect batteries at the end of discharge 
to avoid damaging them.
LVD 1 will close at.  This is the system voltage above which the controller will 
close LVD 1.
Enable battery over temperature LVD1 latch off checkbox.  If this box is checked 
then LVD1 will latch off if a battery over temperature alarm condition occurs (set 
up is in the alarm matrix applet).  LVD1 will remain off even if the temperature falls 
below the alarm off level.  This helps to prevent battery thermal runaway.
LVD1 Control.  Select from Auto , On, Off.  This will normally be set to Auto to 
allow the controller to control the LVD using the On and Off voltage thresholds.  
Selecting On will permanently turn on the LVD.  Selecting Off will permanently 
turn off the LVD.  Note that the On setting is overridden by the over temperature 
latch off function.
Reset LVD Latch off.  This button can be used to reset a system that has latched off 
the LVD in the event of an over temperature condition.  An administrator password 
is required for this function.  Be sure that it is safe to carry out this function before 
doing so.
13.3.6 - Analog I/P - the X75 has no analog input connections.