X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
The Rectifiers tab is used to set up the rectifier type to use with the system. There
are currently three options:
RPCP/M/RSG (I²C based communications)
RRS/RPCG (I²C based communications)
RBSR (PMBus™ based communications)
Enable DC Voltage walk-in checkbox. This allows the system to slowly raise the
system voltage (generated from the rectifiers) in about 30 seconds up to the nominal
voltage. This can be useful to limit load on a generator or slowly increase the battery
charging current. Note that the rectifiers will operate at their default voltage setting
for around 20 seconds before the controller has booted up when a system is first
powered up.
X75 supports RSG type rectifiers, so RPCP/M/RSG is set by default. This setting
should not be changed.
13.3.9 - Current
Figure 20 - Installation WEB Applet - shunts tab (typical)
The Current tab allows a system to be configured to use zero, one or two shunts.
X75 uses a 2 shunt configuration and this is set by default. This setting should not
be changed.