Data Field Descriptions 
 
Defaults (where applicable) are Indicated in Text. 
The following pages list all data fields in this Control (in numerical order). Use the blank programming form 
to record the data for this installation.  Note that both keypad LEDs flash while in Programming mode.  
Note: Entering a number other than the one specified will give unpredictable results. 
  
20 
Installer Code 
Enter 4 digits, 0-9 
 
The Installer Code is used to enter the 4-digit Master Security Code. See 
"Master Code" in the System Operation section for procedure. 
21
 
Quick Arm Enable 
0 = do not allow quick arm 
1 = allow quick arm 
 
If enabled, security code is not required to arm the system. The user 
simply presses and holds down the AWAY or STAY key to arm. 
22
 
Keypad Backlight Timeout 
0 = no timeout; always backlight keys 
1 = turn backlighting off after inactivity 
 
This option allows the choice of either always backlighting the keypad or 
turning the backlighting off after 10 seconds of keypad inactivity. 
23
 
Forced Bypass 
0 = no forced bypass 
1 = provide automatic bypass of all open (faulted) 
zones 
 
All zones bypassed by this function will be displayed after the bypass is 
initiated. 
 
Note:  UL installations:  must be 0 (no forced bypass) 
 
24 
RF House ID Code 
00 = disable all wireless keypad usage 
01-31 = House ID
 
 
The House ID identifies receivers and wireless keypads.  
If a 5827 Wireless Keypad or 5804BD/5804BDV Transmitter is to be 
used, a House ID Code MUST be entered, and the keypad should be set 
to the same ID. 
25
 
Powerline Carrier Device (X-10) House ID 
0 = A 
4 = E 
8 = I 
# + 12 = M 
1 = B 
5 = F 
9 = J 
# + 13 = N 
2 = C 
6 = G 
# + 10 = K 
# + 14 = O 
3 = D 
7 = H 
# + 11 = L 
# + 15 = P 
 
Powerline Carrier Devices require a House ID. This field identifies this 
House ID to the Control.  The Powerline Carrier Devices are 
programmed in field 
✻80. 
 
26
 
Chime by Zone 
0 = no (chimes on fault of any entry/exit or perimeter 
zone when Chime mode is activated 
1 = yes (chimes on fault of those zones assigned to 
Zone List 3 when Chime mode on) 
 
This option allows the installer to define the specific zones intended to 
chime when faulted while the system is in Chime mode. If enabled, these 
zones are defined in zone list 3 (see 
81 Zone List Menu Mode). 
27
 
Real Time Clock Display 
0 = do not display the time 
1 = display the time 
 
Refer to the User’s Manual for setting the clock time and date. 
29
 
Daylight Savings Time Start/End Month 
0, 0 = no daylight saving time used 
1-12 = start month and end month
 
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12. 
30
 
Daylight Savings Time Start/End Week 
0 = disable 
4 = fourth weekend 
1 = first weekend of month  5 = last weekend 
2 = second weekend 
6 = next to last 
3 = third weekend 
7 = 3
rd
 from last 
 
Enter the appropriate start and end weekend of the month. 
31
 
Single Alarm Sounding Per Zone  
(per armed period) 
0 = no limit on alarm sounding per zone 
1 = limit alarm sounding to once per arming period for 
a given zone  
LYNXR/LYNXR24 - Applies to Long Range Radio Output if “0” 
is selected in field ✻91 
LYNXR-EN - Applies to Long Range Radio Output if Long Range 
Radio is connected to the Trigger Single (Neg.) terminal #8.
 
 
UL installations: must be 0 (no limit) 
This field applies only to burglary zones (zone response types 1-5, 10), 
and affects long range radio reporting but does not affect central station 
reporting. 
 
Note: This field applies only to the bell and does not affect keypad 
sounds. 
 
32
 
Fire Sounder Timeout 
0 = yes, fire sounder timeout after time programmed in 
field 
33 
1 = no fire sounder timeout; continue sounding until 
manually turned off 
 
This Control complies with NFPA requirements for temporal pulse 
sounding of fire notification appliances. 
Temporal pulse sounding for a fire alarm consists of the following: 
3 pulses – pause – 3 pulses – pause – 3 pulses. . . 
33
 
Alarm Bell Timeout 
0 = No timeout 
2 = 8 min 
4 = 16 min  
1 = 4 min  
3 = 12 min  
 
This field determines whether the external sounder will shut off after 
time allowed, or continue until manually turned off. 
UL installations: must be set for a minimum of 4 min (option 1) 
34
 
Exit Delay 
00-99 = exit delay time in seconds
 
The system will wait the time entered before sounding an alarm if the 
exit door is left open after the system has been armed. 
UL installations: must be set for a maximum of 60 seconds 
 
 
 