Conducting tests with the TG uni 1 appliance tester:
      in accordance with DIN VDE 0701 and DIN VDE 0702, PC II
Connecting the test object
–  Connect one end of the test line to the probe socket of the tester.
–  Use the crocodile clip to connect the other end of the test line with a
touchable metal part of the housing of the test object.
Ensure that the crocodile clip makes a good contact with the metal part of
the test object.
–  Connect the mains plug of the test object with the test socket of the tester.
–  Switch on the test object with the mains switch.
Switching on the appliance tester
Connect the mains plug of the tester to a properly connected and functional
earthed mains socket. Switch on the tester with the mains switch.
Press the large button in the Switch-on display (Fig. 33).
Entering the test date
The test date is entered or confirmed in the following display (Fig. 33a).
The tester is not equipped with a real-time clock!
Settings for measuring
Press the function button [Test procedure according to standard] in the Main
menu (Fig. 34).
A display with the ‘Settings for measuring’ appears (Fig. 35).
The standard VDE 0701 is preset – change with the [Standard] button. The
protection class is set with the [PC] button (Presetting: PC I). Press the
[PC] button to change the setting to protection class II. Selection of the test
procedure – with or without insulation resistance – is specified with the [Ins
y/n] button.
The headline shows the set measuring method for touch current [DIR.] or
[DIF.] (see ‘Configuration menu’ Point 6.3) and the setting for the manual [H]
or automatic [A] test procedure.
The status line provides information about the current settings throughout the
test procedure.
Fig. 35
Fig. 33
Fig. 34
29
Operating manual for the TG uni 1 appliance tester
Conducting tests in accordance with VDE 0701 and 0702 - PC II
f
f
f
Headline
Status line
Limit values line
f
Fig. 33a
Test procedure:
- manual [H]
- automatic [A]
&
&
&
&
&