Phoenix Contact Type 2 surge protection device VAL-CP-3S-175 2859453 2859453 Datenbogen

Produktcode
2859453
Seite von 8
Nov 14, 2013    2 / 8
Technical data
General
Color
gray
Standards for air and creepage distances
DIN VDE 0110-1
Standards for air and creepage distances
IEC 60664-1
Standards for air and creepage distances
IEC 61643-11
Standards for air and creepage distances
UL 1449
Standards for air and creepage distances
IEEE C62.1
Standards for air and creepage distances
IEEE C62.45
Standards for air and creepage distances
IEC 61643-1
Surge voltage category
III
Pollution degree
2
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
4
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
3L-N & N-PE
Protective circuit
IEC test classification
II
IEC test classification
T2
EN type
T2
Nominal voltage U
N
120 V AC
Maximum continuous operating voltage U
(L-N)
175 V AC
Maximum continuous operating voltage U
C
 (N-PE)
150 V AC
U
T
 (TOV-proof)
208 V AC (5 s)
U
T
 (TOV-proof)
1200 V AC (200 ms / N-PE)
U
T
 (TOV-safe)
240 V AC (5 s)
Nominal frequency f
N
50 Hz
Nominal frequency f
N
60 Hz
Rated load current I
L
40 A (biconnect, 6 mm²)
Rated load current I
L
63 A (2x 10 mm²)
Residual current I
PE
≤ 1 µA
Standby power consumption P
C
≤ 1.75 mW
Max. discharge current I
max
 (8/20) µs maximum (L-N)
120 kA (all channels)
Max. discharge current I
max
 (8/20) µs maximum (N-PE)
40 kA
Nominal discharge current I
n
 (8/20) µs (L-N)
60 kA (all channels)
Nominal discharge current I
n
 (8/20) µs (N-PE)
20 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
≤ 950 V
Voltage protection level U
P
 (L-N)
≤ 850 V
Voltage protection level U
P
 (N-PE)
≤ 950 V
Residual voltage (L-N)
≤ 600 V (at 5 kA)
Residual voltage (L-PE)