Phoenix Contact Type 2 surge protection device VAL-CP-3S-175 2859453 2859453 Datenbogen

Produktcode
2859453
Seite von 8
Nov 14, 2013    3 / 8
Technical data
Protective circuit
Residual voltage (N-PE)
≤ 200 V (at 5 kA)
Response time (L-N)
≤ 25 ns
Response time (L-PE)
≤ 100 ns
Response time (N-PE)
≤ 100 ns
Max. required backup fuse with branch wiring
125 A (gL/gG)
Max. required backup fuse with V-type through wiring
40 A (gL/gG)
Short-circuit resistance I
P
 with max. backup fuse (effective)
25 kA
Short-circuit current self-quenching
100 A (N-PE)
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
16 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
25 mm²
Conductor cross section AWG/kcmil min.
12
Conductor cross section AWG/kcmil max
4
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Pluggable screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Maximum operating voltage U
max.
 AC
250 V AC
Maximum operating voltage U
max
 DC
125 V DC
Max. operating current I
max
1 A AC (inductive)
Max. operating current I
max
1 A AC (ohmic)
Max. operating current I
max
30 mA DC (inductive)