5.7.2  System monitoring 
5.7.2.1  Scheduled logout/login 
Log the INSYS GSM 4.2 easy in and out for a short period every day to allow 
maintenance functions of the GSM provider. Enter the logout time and the 
duration (1 to 98 minutes).  
The INSYS GSM 4.2 easy logs in into the GSM network again afterwards, if the PIN 
of the SIM card is stored. 
5.7.2.2  Periodical logout/login with reset 
In addition, a device reset can be performed for a periodic logout/login with reset.   
The INSYS GSM 4.2 easy logs in into the GSM network again afterwards, if the PIN 
of the SIM card is stored. 
5.7.2.3  Periodic alive message by SMS 
The INSYS GSM 4.2 easy can send an “alive” message to the entered phone 
number as SMS message, daily, weekly or monthly. The LED Status is flashing 
during the dispatch.  
5.7.2.4  Power up SMS 
If this function is active, an SMS is sent with each power up (not Reset). 
 
5.7.3  Date/Time 
Set the real time clock date and time of the INSYS GSM 4.2 easy to a freely 
selected time or to the system time of the configuration PC. 
 
5.7.4  Serial interface 
The parameters for the serial interface depend on the model of the connected 
Moeller device. The compact controllers Moeller easy 500 and 700 communicate 
with 4800 bps 8N1. The compact controllers Moeller easy 800 and MFD 
communicate with 9600 bps and the data format 8N1
 
It is important to set the correct speed. Even if only the easy model is 
replaced (e.g. easy800 for easy500), the speed must be adjusted.