HP Modular Cooling System G2 10642 G2 Expansion Rack AF026A#001 Merkblatt

Produktcode
AF026A#001
Seite von 11
NOTE: For a brief, printer friendly data sheet that describes this product and informs you of the essential capabilities and
specifications, please visit: 
Product Description
HP Modular Cooling System G2 rack is designed for high density server and blade deployments. It re-
circulates and cools the hot server exhaust air through the heat exchanger residing in the MCS G2 unit.
The air is then expelled in front of the enclosed rack at a much lower temperature providing sufficient cool
air for a load of 35kW of servers or blades, or two racks at 17.5kW each.
The MCS G2 unit contains six fans and a heat exchanger deployed along the full height of the rack to
ensure that all the equipment installed receives sufficient chilled air. All fans are swappable while the unit
is online, providing great servicing flexibility. Redundant power is ensured through a failover power switch
that can be connected to two power sources. The environmental monitor controls the air temperature to
the servers and adjusts automatically to meet the pre-established air temperature goal. The environmental
monitor interacts with HP SIM (Systems Insight Manager) via SNMP traps.
The Water Hookup kit is made available as a separate kit to prepare the water hookup ahead of the
arrival of the MCS G2.
A Site Preparation Guide is available for download at:
.
This guide provides details on how to prepare the datacenter for the successful deployment of the MCS
G2. It may be advisable to contact HP Professional Services for a Site Datacenter Thermal Quick
Assessment Service, reference HB691A1 and HB691AE. Visit 
additional information.
The MCS G2 unit mounted next to a HP 10000 G2 Series rack is designed to occupy 1.5 tiles in the
datacenter maintaining tile count for cable routing and access to the plenum.
The MCS G2 and the MCS G2 Expansion Rack are CTO capable with a dynamic load capacity of
2000 Lbs each. For HP CTO services go to:
NOTE: A loaded MCS G2 unit should only be moved by professional movers.
NOTE: We support 3000lbs of static IT Equipment on leveling feet.
Caution: Static loading limits cannot be achieved if the rack is
Not on its leveling feet and
1.
Rolled or pushed from its position.
2.
Not responsible for floor damages where the rack resides. Your floor weight capacity may not support the
full static load capacity. Check with your floor provider before loading.
QuickSpecs
HP Modular Cooling System G2
Standard Features
DA - 12919   Worldwide QuickSpecs — Version 5 — 10.9.2009
Page 4