Benning TRITEST control Multi-Tester 020050 Datenbogen

Produktcode
020050
Seite von 20
B
EN
N
IN
G
B
EN
N
IN
G
B
EN
N
IN
G
B
EN
N
IN
G
B
EN
N
IN
G
B
EN
N
IN
G
L1
L2
L3
TRITEST
®
 control
Benning Elektrotechnik & Elektronik GmbH & Co. KG
Münsterstraße 135 - 137 
D - 46397 Bocholt
Phone: +49 (0) 2871 - 93 - 0   •   Fax: +49 (0) 2871 - 93 - 429
www.benning.de   •   E-Mail: duspol@benning.de
T.-Nr
. 705826.02/ 06-201
1
3
2
9
8
7
6
5
4
J
D
 Bedienungsanleitung
 Operating manual
F
 Mode d‘emploi
E
 
Manuel de instrucciones
  Ръководство за експлоатация
 Návod k použití zkoušečky
 Käyttöohje
 Οδηγίες χρήσεως
H
 Kezelési utasítás
I
 Istruzioni per l’uso
Naudojimosi instrukcija
N
 Bruksanvisning
 Gebruiksaanwijzing
P
 Manual de instrucões
 Instrukcja obsługi
 Instrucţiuni de utilizare
 Инструкция по эксплуатации
S
 Bruksanvisning
  Dutest aletinin kullanma 
tarifnamesi
 Priručnik za upotrebu
Operating manual
TRITEST
®
 control
The phase-sequence indicator TRITEST
®
 control is a 
measuring instrument for testing the phase sequence 
of three-phase mains (subdistributions, sockets etc.). 
The applicable three-phase nominal voltage range 
is 400 V - 690 V, 50 Hz - 60 Hz. As supplementary 
device, the measuring instrument is equipped with an 
integrated battery-powered LED pocket lamp. Before 
using the measuring instrument, carefully read this 
operating manual and always observe the safety 
instructions! 
List of contents
1.  Considerations for use
2.  Safety instructions
3.  Scope of delivery
4.   Functional description of the phase-sequence 
indicator
5.   Battery installation/ battery indication
6.   How to test the phase sequence 
7.   Pocket lamp function
8.   Technical  data
9.   Maintenance
10.  Environmental notice
1.  Considerations for use
This operating manual is addressed to
 
-  professional electricians and
 
-  electrotechnically trained people.
The TRITEST
®
 control is intended for being used in 
dry ambient conditions and must not be used for three-
phase mains with a nominal voltage higher than 690 V 
AC (also see section 9 „Technical data“).
The following symbols are used in this operating man-
ual and on the TRITEST
®
 control:
symbol
meaning
Warning of electric danger!
Indicates instructions that must be 
observed in order to prevent danger for 
people.
Attention! Observe documentation!
This symbol indicates that there are 
instructions in the operating manual that 
must be observed to prevent dangers.
Continuous double or reinforced insula-
tion (protection class II)
Phase sequence clockwise
Phase sequence anti-clockwise
L1
L2 
L3
Connecting marks on the connecting/ 
test cables; phase LEDs signalling 
voltage at L1, L2, L3
This symbol indicates the alignment 
of the batteries for being inserted with 
correct polarity.
Symbol for pocket lamp function
Ground (voltage to ground)
2.  Safety instructions
-   The device is designed and tested according to 
DIN EN 61557-7/ VDE 0413-7, DIN EN 61557-1/ 
VDE 0413-1 and left our works in technically safe 
condition. To preserve this condition and to ensure 
safe operation, the user has to observe all instruc-
tions and warnings contained in this operating 
manual.
 During testing, hold the device by the insulated test 
handles A, B and C only and do not touch the 
testing electrodes (probe tips) !
-   The device may be used only in electrical circuits 
of over voltage category III with a maximum volt-
age of 400 V between the conductor and ground.
 
 With measurements within measurement category 
III, the projecting conductive part of a contact tip 
of the measuring leads must not be longer than 
4 mm.
 
 Prior to carrying out measurements within mea-
surement category III, the push-on caps provided 
with the set and marked with CAT III and CAT IV 
must be pushed onto the contact tips. The purpose 
of this measure is user protection.
-   Before opening the housing cover 4 (battery com-
partment), separate the test handles A, B and C 
from all voltage sources and measuring circuits!
-   Remove the batteries, when you do not use the 
device for a longer period of time! 
-   Do not dispose of used batteries via the house-
hold rubbish! Dispose of those batteries via special 
waste facilities!
-   Please observe: Working on live parts and sys-
tems is dangerous! Even voltages from 30 V AC 
and 60 V DC onwards might involve life-threaten-
ing dangers for people! 
-   Check the device for damages before each meas-
urement. 
-   Always protect the measuring instrument against 
moisture or dampness. Furthermore, protect it 
against contamination and damages! 
-   Protect the device against condensation water. 
Condensation water might form, if the device is 
brought from a cold into a warm environment. 
Thus, the insulating power inside the device might 
be reduced and measuring and insulating faults 
might occur. In such a case, store the device in an 
appropriate environment at a higher temperature 
for approx. 1 hour. 
-   If it can be assumed that safe operation is no long-
er possible, put the device out of operation and 
secure it against unintended operation. 
-   Safe operation is assumed to be no longer pos-
sible, if
 
-   the device exhibits visible damages (housing, 
cable, test handles),
 
-   the device no longer works,
 
-   the device has been stored under unfavour-
able conditions for a longer period of time,
 
-   the device was exposed to mechanical stress 
due to transport.
3.  Scope of delivery
The scope of delivery of the TRITEST
®
 control consists 
of:
 
3.1   one  TRITEST
®
 control with fixed connecting 
cables, L1, L2, L3
 
3.2   one safety probe tip L1, brown (TN 709266)
 
3.3   one safety probe tip L2, black (TN 709267)
 
3.4   one safety probe tip L3, grey (TN 709268)
 
3.5   one safety alligator clip, black (jack Ø = 4 mm, 
TN 709269)
4.   Functional description of the phase-sequence 
indicator
The phase-sequence indicator TRITEST
®
 control  is 
equipped with two integrated voltage divider systems 
with star connection. One of the systems indicates the 
phase LED (indication of the phase voltages L1 9, L2 
7
, L3 5). The other system (combined resistance and 
capacitor) ensures the phase-sequence indication by 
means of two LEDs 8 and 6. The capacitor  (reac-
tive impedance) and the resistances (active resistance) 
build up a phase shift and is almost in phase with a ro-
tary field (travelling wave). The respective LED (clock-
wise 8 or anti-clockwise 6 phase sequence) gets the 
higher voltage and is activated. 
Note:
The phase sequence can be tested even with the bat-
teries being removed or empty. 
5.  Battery installation/ battery indication
Before opening the housing cover 4, separate the 
test handles A, B and C from all voltage sources and 
measuring circuits. 
The battery compartment is behind the housing cover 
4
 at the back of the device. There are apertures on 
the sides of the device to release the cover. For this 
purpose, use a 5.5 mm slotted screwdriver by means 
of which you can move the cover over the holding 
notch with a rotary movement. Thus, the cover can be 
removed.
Please ensure correct polarity when inserting the bat-
teries (see battery symbol)! 
When closing the housing, make sure that the cover 
locks into place correctly and that there is no gap on 
the side of the housing. 
In case of low battery voltage, the pocket lamp cannot 
be operated. Please replace the batteries!
6.  How to test the phase sequence
Contact the connecting cables (test cables) L1, L2, L3 
with the mains to be tested. If necessary, use the probe 
tips A, B and C and the alligator clip J.
The phase voltages are indicated by means of the 
LEDs L1 9, L2 7 und L3 5. 
Depending on the connection, the LED for “clockwise 
phase sequence” 8 or for „anti-clockwise phase se-
quence”  6 is activated.  Please observe for each 
testing that all of the three phase voltages have to be 
present to obtain a correct indication! 
7.  Pocket lamp function
The LED lamp 2 can be switched on via the sliding 
switch  3 integrated into the side of the device. The 
pocket lamp function can be operated independently of 
the phase-sequence indicator system. 
8.  Technical data
-   Regulations, phase-sequence indicator:
 
 DIN EN 61557-7/ VDE 0413-7, DIN EN 61557-1/ 
VDE 0413-1, reference DIN EN 61010-1
-   
Nominal voltage range: 3-phase AC current 
 
400 V - 690 V
-    Maximum rated voltage to earth () and measur-
ing category:
 
With push-on caps: 400 V CAT III
 
Without push-on caps: 400 V CAT II
-   Testing current: ≤ 3,5 mA
-   Nominal frequency range: 50 Hz - 60 Hz
-   Curve behaviour of mains voltage: sinusoidal
-   EMC, resistance to interference: 
 
DIN VDE 0843-20 IEC/ EN 61326
-   Working temperature range: - 10 °C to 50 °C
-   Storing temperature range: - 25 °C to 75 °C
-   Humidity: 80 % to 31 °C, linearly decreasing, 40 % 
to 50 °C, not condensing!
-   Altitude above sea level: 2000 m
 Protection  class:  2 (IEC 60536)
-   Protection type: IP 30 (DIN VDE 0470-1 IEC/  
EN 60529)
 
 3 - first index: Protection against access to danger-
ous parts and protection against solid impurities of 
a diameter > 2.5 mm
 
 0 - second index: No protection against water
-   Degree of contamination: II (IEC 60664)
-   Batteries: 3 round cell batteries 1.5 V (4.5 V, 70 g), 
(IEC/ DIN R6/ LR6)
-   Lamp, LED, power consumption: 25 mA at 4.5 V 
battery voltage
-   Illumination: approx. 30 lux in a distance of 50 cm
-   Usable life of the battery: approx. 100 h with alkali-
manganese batteries
-  
Dimensions: 97 x 59 x 30 mm (without testing cable)
-   Weight: approx. 320 g with measuring accessories 
and battery 
-   Testing cable length: approx. 1000 mm
9. Maintenance
For cleaning the device, use a cloth which is moistened 
with a mild cleaning agent. If there is electrolyte con-
tamination or white deposit near the battery ort he bat-
tery compartment, remove them with a dry cloth. 
Remove the batteries from the device when not using it 
for a longer period of time! 
If the LED lamp 2 does not work any longer or be-
comes weak, replace the batteries by new ones of the 
same type. 
10.  Environmental notice
At the end of the product’s useful life, please 
dispose of it at appropriate collection points 
provided in your country.