6.12  Resetting the module 
The reset to factory default values can be done using the TMCL-IDE. Select SetupConfigure module
the Other tab and then Restore Factory Default
 
If there are communication problems, the reset procedure of the PDx-109-57 is as follows: 
 
1.  Turn OFF the power. 
2.  Link pins 1 and 3 of the programming connector (as shown in the picture below) by hardwire. 
3.  Turn the power ON and wait until the LED on the module flashes fast (faster than normally). 
4.  Turn the power OFF. 
5.  Remove the link between the pins. 
6.  Turn the power ON again and wait until the LED flashes normally (this can take some 
seconds). 
7.  All settings are restored to the factory default now.  
 
 
 
Figure  6.2:  Pins  for  resetting  the 
module