Wago 750-333 PROFIBUS DP/V1 FIELD BUSCOUPLER 12 MBaud 750-333 Datenbogen

Produktcode
750-333
Seite von 154
Fieldbus coupler / controller •  117
Fieldbus Controller 750-833
WAGO-I/O-SYSTEM 750
D R A F T
PROFIBUS
2001-02-27
3.2.9.5 Device 
status
The device status includes the required overhead 7 Byte and transmits internal
status information as well as information relating to the internal bus,
PROFIBUS-DP and the PFC running time system to the master or the higher
ranking controls.
Byte
Information
Meaning
15
0
0
0
0
0
1
1
1
Header  byte
(7 Byte status information
incl. header)
16
1
0
1
0
0
0
0
0
Status  type
(manufacturer specific device status)
17
0
0
0
0
0
0
0
0
Slot  number  0
18
0
0
0
0
0
0
0
0
Status  differentiation
(none)
19
q
q
n
n
n
n
n
n
Status  message
q – Status source
'00'
Internal status
'01'
Internal bus status
'10'
PROFIBUS DP status
'11'
PFC-RTS status
n – Status number
20
x
x
x
x
x
x
x
x
Status  argument
21
0
0
0
0
0
0
0
0
Reserved