Wago 750-333 PROFIBUS DP/V1 FIELD BUSCOUPLER 12 MBaud 750-333 Datenbogen

Produktcode
750-333
Seite von 154
Fieldbus coupler / controller •  119
Fieldbus Controller 750-833
WAGO-I/O-SYSTEM 750
D R A F T
PROFIBUS
2001-02-27
3.2.9.5.3 
PROFIBUS-DP status messages and arguments
Status
message
Status
argument
Description
0x81
0x01
Insufficient parameter data configuration data
0x81
0x02
Excessive parameterisation data
0x82
n
Faulty n. parameterisation byte
0x83
0x01
Insufficient configuration data
0x83
0x02
Excessive configuration data
0x84
n
Faulty n. configuration byte (module)
0x85
0x01
Maximum input data length exceeded
0x85
0x02
Maximum output data length exceeded
0x86
0x01
Compilate buffer overflow for DP process image
0x86
0x02
Compilate buffer overflow for PFC process image
3.2.9.5.4 
PFC-RTS status messages and arguments
Status
message
Status
argument
Description
0xC1
0x00
t. b. d.
0xC1
0x01
t. b. d.
0xC2
0x00
t. b. d.