D R A F T
PROFIBUS
2001-02-27
3.1.10 LED 
signalling
The coupler possesses several LED’s for on site signalling of the coupler oper-
ating status or the complete node
24V 0V
+ +
RUN
BF
DIA
BUS
I/O
PROFIBUS
C
D
B
A
Fig. 3-10: Display elements 750-333
g012106x
3.1.10.1 Blink 
code
Detailed fault messages are displayed with the aid of a blink code. A fault is
cyclically displayed with up to 3 blink sequences.
•  The first blink sequence (approx. 10 Hz) starts the fault display.
•  The second blink sequence (approx. 1 Hz) following a pause. The number
of blink pulses indicates the fault code.
•  The third blink sequence (approx. 1 Hz) follows after a further pause. The
number of blink pulses indicates the fault argument.