WAGO-I/O-SYSTEM 750
2001-02-27
PROFIBUS
3.1.10.2 Fieldbus 
status
The upper four LED´s signal the operating conditions of the PROFIBUS
communication.
LED
Colour
Meaning
RUN
green
The 'RUN' LED indicates to the user if the fieldbus coupler is per-
fectly initialised.
BF
red
The 'BF' LED indicates that the communication functions via the
PROFIBUS.
DIA
red
The 'DIA' LED indicates an external diagnosis.
BUS
red
The 'BUS' LED signals a projecting fault.
RUN
BF
DIA
BUS
Meaning
off
off
off
off
No operating voltage to the coupler (status LED of
the bus coupler supply does not light up) or a
hardware fault is present.
on
on
*
off
PROFIBUS interface started, baud rate was not yet
recognised.
on
blinks
*
off
Baud rate recognised, station not yet parameterised
and configured.
on
blinks
on
blinks
cycli-
cally
Slave was incorrectly projected.
Fault message via blink code
on
off
*
off
The coupler is exchanging data.
on
*
on
*
The coupler signals an existing diagnosis.
* Not relevant