Weidmueller Weidmüller 1175980000 ACT20M-CI-CO-S Measuring Transducer Content: 1 pc(s) 1175980000 Datenbogen
Produktcode
1175980000
Datenblatt
ACT20M
ACT20M-CI-CO-S
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technische Daten
Erstellungs-Datum December 17, 2013 12:58:05 PM CET
Katalogstand xx.xx.xxxx / Technische Änderungen vorbehalten
2
Dimensions and weights
Width
6.1 mm
Height
112.5 mm
Depth
114.3 mm
Net weight
80 g
Temperatures
Humidity
40 °C / 93 % rel. humidity,
no condensation
Operating temperature
-25 °C...+70 °C
Ambient temperature
-25 °C...+70 °C
Storage temperature
-40 °C...+85 °C
Probability of failure
MTBF
284 Years
Input
Supply voltage
24 V DC ± 30 %
Voltage drop, current input
< 1.5 V
Input current
0...20 mA, 4…20mA
Temperature input range
Configurable
Voltage drop
<1,5 V
Output
Cut-off frequency (-3 dB)
100 Hz
Number of outputs
1
load impedance current
≤ 600 Ω, @ max 23mA
Output current
0...20 mA, 4...20 mA
General data
Accuracy
< 0.05 % of measuring
range
Configuration
none
Galvanic isolation
3-way isolator
Mounting rail
TS 35
Power consumption, max.
0.8 W
Power consumption, typ.
400 mW
Step response time
≤ 7 ms
Supply voltage
24 V DC ± 30 %
Temperature coefficient
≤ 0.01 % / °C
Type of connection
Screw connection
Insulation coordination
EMC standards
EN 61326-1
Galvanic isolation
3-way isolator
Insulation voltage
2.5 kV
eff
Pollution severity
2
Rated voltage
300 V
eff
Standards
DIN EN 61010-1, DIN EN
60079, DIN EN 61326-1
Surge voltage category
II
Ratings IECEx/ATEX
Certificate No. (ATEX)
KEMA10ATEX0183X
Certificate No. (IECEX)
IECEXKEM10.0090X
Classifications
ETIM 3.0
EC002479
eClass 6.2
27-21-01-20
eClass 7.1
27-21-01-20
Product information
Descriptive text technical data
Power supply optionally over the DIN mounting rail CH20M
Descriptive text accessories
DIN mounting rail, see Accessories