│ 7. Installation 
 
18 
 
ECA 100 ipro standard model units 
can be operated at two levels with 
double switches. Without a double 
switch, the fan can either be opera-
ted at performance level 1 or perfor-
mance level 2, see switch variants in 
Chapter 13. 
4.  Check position of cable grommet. It must 
be well sealed. 
 
7.3 Operating programs  
●  VZC, KVZC, F, KF, B and KB: One of the 
4 following operating programs can be set 
with jumpers J4 and J5. 
●  H and KH: One of the 4 following opera-
ting programs can be set with jumpers J4 
and J5 and the light switch connected in 
accordance with chapter 13. If this is 
switched on, it takes priority over the 
automatic humidity process. 
●  Comfort program (supplied in this mode), 
night program, economy program and 
power program. 
 
1.  Set the operating program you want with 
jumpers J4 and J5. 
 
Comfort program 
●  Performance level 1 while room is being 
used, performance level 2 during overrun 
time. 
●  J4 bridged, J5 bridged 
 
Night program 
●  Performance level 2 while room is being 
used, performance level 1 during overrun 
time.  
●  J4 open, J5 open 
 
 
Economy program 
●  Performance level 1 during operation and 
overrun. 
●  J4 open, J5 bridged 
 
 
Power program 
●  Performance level 2 during operation and 
overrun. 
●  J4 bridged, J5 open