4 - CONTROL MODULE
4.5 Theory of Operation
User Interface Display
Explanation
STANDBY
Boiler operates in standby mode until Central Heat (CH) or 
Domestic Hot Water (DHW) demand detected.
Access User Menu by pressing ‘Menu’ key on user interface.
User Menu
User Menu
User Menu structure. Use scroll keys to move to desired menu, 
and press Enter.
•  ‘Boiler Status’ submenu
•  ‘Settings’ submenu – View CH , DHW supply water set 
point.
•  ‘Cascade Status’ submenu – Boiler set to function as 
part of multiple boiler installation; submenu used to view  
runtime parameters. See Multiple Boiler Manual.
Boiler Status
Supply Temperature set point displayed.
CH set point displayed if boiler running in CH mode.
Note: Value may change in proportion to outdoor 
temperature when running in Outdoor Reset mode.
DHW supply set point displayed if boiler is running in DHW 
mode.
Water Temperature leaving boiler heat exchanger.
Water Temperature entering boiler heat exchanger.
Heat Exchanger Pump status (On or Off)
CH/System Pump status (if used, On or Off)
DHW Pump status (if used, On or Off)
DHW Thermostat (open or closed)
System Water Temperature (if used)
Vent System Temperature
Outdoor Temperature (if used)