Acidic nature of flue gasses condensing on aluminum boiler 
sections cause formation of aluminum oxide. This oxide 
formation is normal, is generally uniform throughout boiler 
sections, and represents negligible mass of aluminum that 
is consumed by oxidation during life of boiler. 
If left unchecked, this buildup may eventually cause 
blockage of flue gas passages in boiler sections, reducing 
efficiency, and ultimately shutting down boiler due to lack 
of combustion air flow. 
Regular service and maintenance by qualified 
service agency must be performed to assure safe 
trouble free operation and maximum efficiency. It is 
recommended to service boiler at least once every 12 
months.
Beginning Of Each Heating Season
1. 
 Schedule annual service call by qualified service 
agency, which includes:
A.  Examine flue passages between boiler sections, 
burner, and condensate lines, and clean if 
necessary following annual examination and 
cleaning instructions in paragraph F (below).
B.  Visually inspect venting and air intake system for 
proper operation. If vent or air intake show any 
signs of deterioration or leakage, repair or replace 
immediately. Ensure proper re-assembly and re-
sealing of vent and air intake system.
C.  Check for and remove any obstruction to flow of 
combustion air or venting of flue gases. 
D.  Follow instructions for “Startup” on page 28.
E.  Follow “Checkout Procedure & Adjustments” on 
page 35.
F.  Visually inspect condensate drain line for proper 
operation. Check for deteriorated or plugged 
condensate drain line.
G.  Check all gasket joints for leakage, and tighten 
bolts or replace gaskets if necessary.
H.  Remove jacket front and top panels and check for 
piping leaks around relief valve and other fittings. 
Repair, if found. DO NOT use stop leak compounds.
2. 
Check boiler area is free from combustible materials, 
gasoline, and other flammable vapors and liquids.
3. 
Circulator pump and blower motor furnished with boiler 
are permanently lubricated from factory and require 
no further lubrication. Lubricate additional or non-
factory supplied pumps and/or motors according to 
manufacturer’s instruction.
Daily During Heating Season
1. 
Check for and remove any obstruction to flow of 
combustion air or venting of flue gases.
2. 
Check boiler area is free from combustible materials, 
gasoline, and other flammable vapors and liquids.
Monthly During Heating Season
1. 
Remove jacket front and top panels. Check for piping 
leaks around relief valve and other fittings. If found, 
contact qualified service agency to repair. DO NOT use 
stop leak compounds.
2. 
Test relief valve. Refer to valve manufacturer’s 
instructions packaged with relief valve.
3. 
Visually inspect venting and air intake system for 
proper function. If vent or air intake show any signs 
of deterioration or leakage, contact qualified service 
agency to repair or replace immediately and ensure 
proper reassembly and resealing of vent and air intake 
system.
4. 
Visually inspect PVC condensate drain pipe for proper 
operation. If drain pipe shows any signs of blockage, 
leakage, or deterioration contact qualified service 
agency to clean, repair, or replace immediately.
5. 
Check air vent(s) for leakage.
Periodically During Heating Season
Where low water cutoffs are used, periodic inspection of 
low water cutoff is necessary, including flushing of float 
type devices. Refer to low water cut off manufacturer’s 
specific instructions.
16 - MAINTENANCE AND CLEANING