B&B Electronics RS-232 to J1939 Converter CE 1939STB Benutzerhandbuch

Seite von 40
1939STB4600 Manual 
 
 
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 
B&B Electronics Ltd – Westlink Commercial  Park – Oranmore, Galway, Ireland – Ph +353 91 792444 – Fax +353 91 792445 
 
 
Control Byte 4 
 
When control byte 3 is set to “external commands” (bit 4 set to 1), nibble 
1 of control byte 4 is used to tell the J1939 in which message slot location (1 
through 15) to place the message data.  NOTE: Message location number 15 
is receive only. 
  
 
When control byte 3 is set to “ internal commands” (bit 5 set to 1), nibble 
1 of control byte 4 has the following functions: 
 
 
Nibble 2 of control byte 4 is reserved for future use and is set to 0. 
Table 7.  Byte 4 
                        Nibble 2 
                  Nibble 1 
 Bit  7 
Bit 6 
Bit 5 
Bit 4 
Bit 3 
Bit 2 
Bit 1 
Bit 0 
Table 8.  Nibble 1 Bit Values 
Nibble 1 Value 
Function 
      0001 
Display vender number & version 
      0010 
Set baud rate, stop, start bits 
      0100 
Not  used 
      1000 
Not  used