Hamilton Sundstrand Company Fuel Metering Valves XVG Benutzerhandbuch

Seite von 36
 
 
 
Register 
Number 
XVG/eXVG Parameters 
Name 
Write 
Access 
Description Type 
7072 7073 
IDM_FVOLTSNEG15 
RO 
Fault Log, VoltsNeg15 at time of fault 
Float
 
7074 7075 
IDM_TEMPAMB 
W3 
Approx. ambient temp. of electronics cavity, deg C 
Float
 
7076 7077 
IDM_AUTOADCAGAIN 
RO 
AUTO ADC A gain, range 0.95 to 1.05 
Float
 
7078 7079 
IDM_AUTOADCBGAIN 
RO 
AUTO ADC B gain, range 0.95 to 1.05 
Float
 
7080 7081 
IDM_AUTOADCAOFF 
RO 
AUTO ADC A offset, range -80 to 80 counts 
Float
 
7082 7083 
IDM_AUTOADCBOFF 
RO 
AUTO ADC B offset, range -80 to 80 counts 
Float
 
7084 7085 
IDM_VOLTSPOS15 
RO 
+15V supply voltage, Volts 
Float
 
7086 7087 
IDM_VOLTSNEG15 
RO 
-15V supply voltage, Volts 
Float
 
7088 7089 
IDM_XMEAS 
RO 
Same as PosInInches 
Float
 
7090 7091 
IDM_XCMD 
RO 
Commanded position, inches 
Float
 
7092 7093 
IDM_XERR 
RO 
Position error, inches 
Float
 
7094 7095 
IDM_INTXERR 
RO 
Position control integral command, velocity 
(in/0.0001sec) 
Float
 
7096 7097 
IDM_VCMD 
RO 
Velocity command (in/0.0001sec) 
Float
 
7098 7099 
IDM_ICMD 
RO 
Motor current command, counts 
Float
 
7100 7101 
IDM_VMEAS 
RO 
Measured velocity (in/0.0001sec) 
Float
 
7102 7103 
IDM_GASTEMPC 
RO 
Gas temperature in Celsius (includes TempOff), used 
for LVDT position compensation & analog output 
Float
 
7104 7105 
IDM_MOTORCUR 
RO 
Motor current, approximation in Amps 
Float
 
7106 7107 
IDM_TIT 
RO 
Total inches traveled 
Float
 
7108 7109 
IDM_DJSUM 
RO 
Total demand jitter, volts 
Float
 
7110 7111 
IDM_SLR 
RO 
Seal life remaining, % (based on IDM_TITHRESH) 
Float
 
7112 7113 
IDM_APLUSBV 
RO 
LVDT A+B voltage measurement 
Float
 
7114 7115 
IDM_AMINUSBV 
RO 
LVDT A-B voltage measurement 
Float
 
 
Table 22:  Real Time Status Parameters 
 
10 
Write Modbus Application 
 
Software packages that support Modbus protocol could be used to write Modbus 
application for the XVG/eXVG.  The necessary Modbus functions are Read 
Registers, Write Single Register, and Write Multiple Registers. 
 
-  All XVG/eXVG Modbus parameters are readable using Read Register 
function. 
-  Write to the writeable registers can be accomplished with Write functions and 
appropriate password. 
 
User Responsibility 
 
By using the Modbus read and write functions, it is possible to access all of the 
XVG/eXVG parameters, features, and functions.  The following precautions must 
be considered when writing your own Modbus application: 
 31