Hamilton Sundstrand Company Fuel Metering Valves XVG Benutzerhandbuch

Seite von 36
 
 
 
 
-  Only one host master can send request message at a time. 
-  Each XVG/eXVG unit on the same network must have a unique address. 
-  Adhere to the tables of registers provided and their allowable data range.   
-  Do not attempt to write to any register if you are not sure of the consequence.   
-  Do not write to registers that are for options your XVG/eXVG does not have.   
 
Failure to do so can result in erratic control and/or damage to equipment.  Care 
must also be taken that the process cannot cause damage to property or injury to 
personnel if the wrong commands are sent due to operator error or equipment 
malfunction. 
 
Handling Communication Errors 
 
-  Reading from or writing to a register that does not exist or is currently 
disabled will result in a “time-out response”, or in other words, the 
XVG/eXVG will not reply with a message. 
-  Messages with the wrong format, timing, or CRC are ignored.   
-  Writing to a read-only register, writing with out-of-range data, or writing with 
improper permission will result in response error messages.  
-  It is the user’s responsibility to handle the error appropriately and determine 
whether to resend the message or halt the operation. 
 
Following are a few sample procedures for XVG/eXVG Modbus application: 
 
10.1  Real-Time Status & Parameters Upload Procedure 
 
Following are examples of the real time parameters that can be read at anytime. 
 
Register 
Number 
XVG/eXVG Parameter Name 
Description 
Type 
7000 
IDM_POSININCHES 
Valve Position in inches 
Float 
7002 
IDM_INPUTPRES 
Input Pressure, PSIA 
Float
 
7004 IDM_OUTPUTPRES 
Output 
Pressure, 
PSIA 
Float
 
7008 
IDM_MEASFLOW 
Measured Flow, PPH 
Float
 
7014 
IDM_GASTEMP 
Gas Temperature, degrees F (includes TEMPOFF) 
Float
 
7016 
IDM_VOLTS3PT3 
3.3V supply voltage, Volts 
Float
 
7018 IDM_PRESSRATIO 
Pressure 
Ratio 
Float
 
7020 
IDM_DMDININCHES 
Position Demand in inches 
Float
 
7074 
IDM_TEMPAMB 
Approx. ambient temp. of electronics cavity, deg C 
Float
 
7084 
IDM_VOLTSPOS15 
+15V supply voltage, Volts 
Float
 
7086 
IDM_VOLTSNEG15 
-15V supply voltage, Volts 
Float
 
7104 
IDM_MOTORCUR 
Motor current, approximation in Amps 
Float
 
7106 
IDM_TIT 
Total inches traveled 
Float
 
 
Table 23:  Parameters Upload for Status 
 