Barnet Ensign Ross ED810 Benutzerhandbuch

Seite von 10
ED810 INSTRUCTION MANUAL  27-02-07 
2
IMPORTANT 
 
1. 
The  equipment supplied must not be modified in any way since modifications will 
invalidate intrinsic safety certification, MCA and Lloyds approval. 
 
2. 
Care should be taken during servicing as high voltages may be present on the output 
contacts. 
 
3. 
It is important to note that the ED810 contains four Zener Barriers, type ZB1, which are 
“potted” in epoxy resin.  The Zener Barriers contain fuses which once damaged are not 
replaceable.  The fuses inside the Zener Barrier will blow if even temporary short circuits 
are placed on the sensor wiring thus rendering the Zener Barrier inoperable and not 
repairable.  Great care should therefore be taken to avoid inadvertent short circuits. 
 
4. 
Electronic Devices strongly recommend consultation of the HSE publication EH40, 
which lists the permitted levels of exposure to most toxic gases. 
 
 
ATEX ESSENTIAL SAFETY REQUIREMENTS 
 
The ED810 gas detector, internally mounted Zener Barriers and associated gas sensors are 
ATEX certified Intrinsically Safe and the following important requirements need to be 
followed. 
 
 
1. 
The equipment must only be installed, operated and maintained by trained competent 
personnel. 
 
2. 
This apparatus has been designed in accordance with EN50 014 and EN50 020,  
therefore the apparatus has been designed to meet the fault tolerant requirements of 
Associate Apparatus for Category 'ia'. 
 
3. 
The installation and maintenance must be in accordance with all appropriate 
international, national and local standard codes of practice and site regulations for 
intrinsically safe apparatus. 
 
4. 
The  installation  and  maintenance  must  be  in  accordance  with  the  instructions 
contained in this installation and maintenance manual. 
 
5. 
Access to the circuitry must not be made during operation. 
 
6. 
This product is an associated electrical apparatus and must not be installed in the 
 
hazardous area without the provision of further certified hazardous area protection. 
 
7. 
The product must not be subjected to mechanical and thermal stresses in excess of  
those permitted in the certification documentation and the instruction manual.  If 
necessary the product must be protected by an enclosure to prevent mechanical 
damage. 
 
8. 
The product must not be installed in a position where it may be attacked by 
aggressive substances. 
 
9. 
The product must be protected from excessive dust by an enclosure etc. 
 
10. 
The product can not be repaired by the user and must be replaced by an equivalent 
certified product. Repairs should only be carried out by the manufacturer or approved 
service centre.