York R123 Benutzerhandbuch

Seite von 156
YORK INTERNATIONAL
106
FORM 160.55-O1 (604)
Enabled  by  a  Service  Technician  (fol low ing  in struc tions 
in Service Manual 160.55-M1) and the Leaving Chilled 
Liquid temperature Setpoint is <38.0°F.
EVAPORATOR – TRANSDUCER OR LEAV ING 
LIQUID PROBE

A possible defective Evaporator pressure Transducer 
or Leaving Chilled Liquid temperature Thermistor has 
been detected. The pressure and temperature that these 
devices are indicating are not in the correct re la tion ship 
to each other. The OptiView Control Center con verts the 
evap o ra tor  pressure  to  a  Saturated  Tem per a ture  value 
and compares this value to the Leaving Chilled Liquid 
tem per a ture (difference = chilled liquid temp – evap o -
ra tor saturated temp). The difference should not be out-
 side the range of –2.5°F to +25.0°F. If the Transducer 
and Thermistor are accurate, the Evap o ra tor Saturated 
tem per a ture should not be > 2.5°F warm er nor > 25.0°F 
colder than the leaving chilled liq uid temperature. In or-
 der to initiate a shutdown, the dif fer ence must be out side 
the acceptable range con tin u ous ly for 10 minutes. For 
Steam Turbine drive ap pli ca tions, this check is by passed 
for the Þ rst 20 min utes of chiller operation. The chiller 
can be started af ter the COMPRESSOR switch is placed 
in the Stop-Reset (O) position. 
EVAPORATOR – TRANSDUCER OR 
TEMPERATURE SENSOR

A possible defective Evaporator pressure Transducer 
or Refrigerant Temperature Sensor has been detected. 
The OptiView Control Center converts the evaporator 
pressure to a Saturated Temperature value and com-
 pares this value to the optional Evaporator Refrigerant 
Tem per a ture Sensor. If the difference between these 
tem per a tures is greater than 3.0°F, continuously for 1 
minute, this shutdown is performed. This check is only 
performed under the following conditions: 
  •    Chiller has been running for at least 10 minutes
  •    Evaporator Refrigerant temperature (RT7) has been 
enabled by a Service technician using in struc tions 
in YORK Service Manual 160.55.M1
  •    Not in Brine cooling mode 
  •    Smart Freeze is enabled (Flash Memory Card ver-
 sion C.MLM.02.02.xxx and later)
 •   Evaporator Temperature Sensor (RT7) or Evap o -
ra tor Saturation Temperature is indicating a tem-
 per a ture of <32.0ºF (Flash Memory Card version 
C.MLM.02.02.xxx and later) 
  
The chill er can be start ed af ter the tem per a tures are 
within 3.0°F of one another and the COM PRES SOR 
switch is placed in the Stop-re set (O) po si tion.  
CONDENSER – HIGH PRES SURE 
CONTACTS OPEN

The contacts of the electro-mechanical high pressure 
safety device, located on the condenser shell, have 
opened be cause this device has detected a pressure > 
29.7 PSIA. The contacts will automatically close when 
the  con dens er  pressure  de creas es  to  <  23.7  PSIA.  The 
chill er can be started after the contacts close and the 
COM PRES SOR switch is placed in the Stop-Re set 
(O)  po si tion. 
  
CONDENSER – HIGH PRESSURE
The condenser pressure, as sensed by the Condenser 
Transducer, has increased to >29.7 PSIA. The chiller 
can be start ed after the pressure decreases to <23.7 PSIA 
and the COM PRES SOR switch is placed in the Stop-
Reset (O) position. 
“CONDENSER – HIGH PRESSURE – 
STOPPED”
(Software versions C.MLM.02.06.xxx and later or 
C.OPT.02.06.303 and later)
The condenser pressure exceeded 26.7 PSIA while the 
chiller was stopped. High temperature condenser water 
ß owing through the condenser while the chiller is shut-
down can   cause a condenser high pressure condition 
resulting in loss of refrigerant. This safety fault antici-
pates this problem by annunciating the condenser high 
pressure condition. The chiller  can be restarted after a 
Service Technician performs a special reset preset proce-
dure  contained in YORK Service Manual 160.55-M1.
CONDENSER – PRESSURE TRANSDUCER OUT 
OF RANGE

The Condenser Pressure Transducer is indicating a 
pres sure that is >35.3 PSIA. This is outside the nor mal 
op er at ing range of the trans duc er. This is generally in-
 di cates a defective trans duc er. The chiller can be start ed 
after the transducer is in di cat ing a pressure that is < 35.3 
PSIA and the COM PRES SOR switch is placed in the 
Stop-Reset  (O)  po si tion.
AUXILIARY SAFETY – CONTACTS CLOSED
The Auxiliary Safety shutdown contacts, connected 
to I/O Board TB4-31 have closed, initiating a safety 
shut down. This input is a general-purpose, user deÞ ned 
safe ty shutdown input. The chiller can be started after 
the con tacts open and the COM PRES SOR switch is 
placed in the Stop-Reset (O) position.  
OptiView Control Center