DISCHARGE – HIGH TEMPERATURE
The discharge temperature, as sensed by the Dis charge 
Temperature Thermistor, has increased to > 220.0°F. The 
chiller can be started after the tem per a ture de creas es to 
< 220.0°F and the COMPRESSOR switch is placed in 
the Stop-Reset (O) position. 
DISCHARGE – LOW TEMPERATURE
The discharge temperature, as sensed by the Dis charge 
Temperature Thermistor, has decreased to < 30.0°F. The 
chiller can be started after the tem per a ture in creas es to 
> 30.0°F and the COMPRESSOR switch is placed in 
the Stop-Reset (O) position. 
OIL – HIGH TEMPERATURE
The oil temperature, as sensed by the Oil Temperature 
Thermistor, has increased to > 180.0°F. The chiller can 
be started after the temperature decreases to < 180.0°F 
and the Compressor switch is placed in the Stop-Re set 
(O) position. 
OIL – LOW DIFFERENTIAL PRESSURE
The differential oil pressure decreased to < 15.0 PSID 
while the chiller was running or failed to achieve 20.0 
PSID during the last 5 seconds of the “System Prelube” 
pe ri od. The differential oil pressure is the difference 
be tween the output of the Sump Oil Pressure Trans duc er 
(system low pressure) and the output of the Pump Oil 
Pressure Transducer (system high pres sure). The chill er 
can be started after the COM PRES SOR switch is placed 
in the Stop-Reset (O) position. 
OIL - HIGH DIFFERENTIAL PRESSURE
The differential oil Pressure increased to > 60.0 PSID 
while the oil pump was running. The differential oil 
pres sure is the difference between the output of the 
Sump Oil Pressure Transducer (system low pressure) 
and the output of the Pump Oil Pressure Transducer 
(system high pressure). The chiller can be started after 
the dif fer en tial oil pressure decreases to < 60.0 PSID 
and the COMPRESSOR switch is placed in the Stop-
reset (O) position. 
CONTROL PANEL – POWER FAILURE
A Control Power failure has occurred. If the power 
fail ure duration was < the duration of the applicable 
“Coastdown” period (2.5 minutes standard; 15 min utes 
steam turbine), the remainder of the “Coastdown” is 
performed upon restoration of power. The chiller can 
be started after the COMPRESSOR switch is placed in 
the Stop-reset (O) position. This message can in di cate 
a Cycling (auto-restart after power failure) or Safe ty 
(manual restart after power failure) shutdown, de pend ing 
upon Control Center conÞ guration. It indicates a Cy-
cling shutdown when displayed in orange char ac ters; 
Safety shutdown when displayed in red char ac ters. The 
OptiView Control center is conÞ gured for auto-restart 
or manual restart after power failure by a qualiÞ ed Ser-
 vice tech ni cian following instructions in YORK Service 
Manual 160.55-M1. 
MOTOR OR STARTER – CURRENT 
IMBALANCE

The three phase com pres sor mo tor current imbalance 
was > 30% con tin u ous ly for 45 sec onds. The imbalance 
is not checked until the chill er has been running for at 
least 45 seconds and the av er age of the three phases of 
motor current is > 80% of the pro grammed 100% chiller 
Full Load Amps. The av er age is calculated as: Iave = 
(Ia+Ib+Ic) ÷ 3. The im bal ance is calculated as:
(Ia-Iave) + (Ib-Iave) + (Ic-Iave)  x 100
 
   
 2(Iave)
The Style B Solid State Starter detects the unbalance 
condition and advise the Optiview Control Center 
Microboard via serial communications. The Style A 
Solid State Starter and Variable Speed Drives returns 
the 3-phase motor current values to the Optiview Control 
Center Microboard where the unbalance calculation is 
performed. This safety shutdown is not performed on 
Electro-mechanical starter applications
WATCHDOG – SOFTWARE REBOOT
The Microboard’s software Watchdog initiated a Mi-
 cro pro ces sor reset because it detected that a portion of 
the chiller op er at ing Program was not be ing executed. 
The result of this reset is a Safety shut down and re-ini-
tialization of the Program. This is generally in dic a tive 
of a severe elec tri cal power disturbance or im pend ing 
Microboard Failure. The chill er can be start ed af ter the 
COM PRES SOR switch is placed in the Stop-Re set (O) 
po si tion. 
“SURGE PROTECTION – EXCESS SURGE”
(Flash Memory Card version C.MLM.02.02.xxx 
and later)
(Applies only if Surge Protection SHUTDOWN fea ture 
is Enabled) The Surge Window Count surge events ex-
ceeded the Count Limit setpoint. If the Surge Pro tec tion 
Ex tend ed Run feature is Disabled, the chiller shutsdown 
as soon as the count exceeds the limit. If the Ex tend ed 
Run feature is Enabled, this shutdown oc curs only if the 
count exceeds the limit at completion of the 10 minute 
Ex tend ed Run period. The chiller can be start ed after 
the COMPRESSOR Switch is placed in the Stop-Reset 
(O) position. 